9469300991 Rev A

Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Group Register Type Bytes R/W

Unit

Range

Time

DST End Month

GG

0186

Uint32 4

R W n/a

January=0
February=1

March=2

April=3
May=4

June=5
July=6

August=7
September=8

October=9

November=10
December=11

Time

DST End Day

GG

0188

Uint32 4

R W n/a

1 - 31

Time

DST End Week Of Month

GG

0190

Uint32 4

R W n/a

First=0
Second=1

Third=2
Fourth=3
Last=4

Time

DST End Day Of Week

GG

0192

Uint32 4

R W n/a

Sunday=0

Monday=1
Tuesday=2

Wednesday=3

Thursday=4
Friday=5

Saturday=6

Time

DST End Hour

GG

0194

Uint32 4

R W n/a

0 - 23

Time

DST End Minute

GG

0196

Uint32 4

R W n/a

0 - 59

Time

DST Bias Hours

GG

0198

Int32

4

R W n/a

-23 - 23

Time

DST Bias Minutes

GG

0200

Int32

4

R W n/a

-59 - 59

Time

Twelve-Hour Mode

GG

0202

Uint32 4

R W n/a

12 Hour Mode=0

24 Hour Mode=1

Time

Date Format

GG

0204

Uint32 4

R W n/a

YYYY-MM-DD=0

MM-DD-YYYY=1
DD-MM-YYYY=2

Unit Information

Style Number

GG

0206

String 32

R W n/a

0 - 32

Unit Information

Serial Number

GG

0222

String 32

R W n/a

0 - 32

Load Detection

EPS Threshold

GG

0238

Uint32 4

R W Percent

3 - 10

Load Detection

Low-Line Scale

GG

0240

Float

4

R W n/a

0.001 - 3

Load Share Settings

System Type

GG

0242

Uint32 4

R W n/a

Single Generator=0

Multiple
Generator=1

Load Share Settings

Enable Comms Fail Pre Alarm

GG

0244

Uint32 4

R W n/a

Disabled=0

Enabled=1

Auto Restart

Auto Restart Enable

GG

0246

Uint32 4

R W n/a

No=0

Yes=1

Auto Restart

Auto Restart Timeout Sec

GG

0248

Uint32 4

R W Second

30 - 1800

Auto Restart

Auto Restart Attempts

GG

0250

Uint32 4

R W n/a

1 - 10

ECU Config

CANBus Enabled By User

GG

0252

Uint32 4

R W n/a

Disabled=0
Enabled=1

ECU Config

DTC Enable

GG

0254

Uint32 4

R W n/a

Disabled=0
Enabled=1

ECU Config

J1939 Source Address

GG

0256

Uint32 4

R W n/a

1 - 253

ECU Config

ECU Control Output

GG

0258

Uint32 4

R W n/a

FL CNTCT=0
PS CNTCT=1

ECU Config

Pulsing Enable

GG

0260

Uint32 4

R W n/a

Disabled=0
Enabled=1

ECU Config

ECU Settling Time

GG

0262

Uint32 4

R W Millisecond 5500 - 30000

ECU Config

ECU Pulse Cycle Time

GG

0264

Uint32 4

R W Minute

1 - 60

ECU Config

ECU Disconnect Time

GG

0266

Uint32 4

R W Second

1 - 60

ECU Config

ECU Connect Time

GG

0268

Uint32 4

R W Second

1 - 60

ECU Config

CAN Bus Eng Ctrl Param Transmit Enable GG

0270

Uint32 4

R W n/a

Disabled=0
Enabled=1

ECU Config

Requested MTU SMC Eng Operating
Mode

GG

0272

Uint32 4

R W n/a

1 - 2

ECU Config

SPN Conversion Method

GG

0274

Uint32 4

R W n/a

1 - 4

ECU Config

Voltage Regulator CANbus type

GG

0276

Uint32 4

R W n/a

None=0

Marathon=1
Basler=2

J1939=3

ECU Config

Voltage Regulator Primary Voltage

Setpoint

GG

0278

Uint32 4

R W Decivolt

1000 - 6000

ECU Config

Voltage Regulator Alternate Voltage
Setpoint

GG

0280

Uint32 4

R W Decivolt

1000 - 6000

ECU Config

Voltage Regulator Voltage Adjust
Bandwidth

GG

0282

Uint32 4

R W Centivolt

0 - 3000

ECU Config

Voltage Regulator Field Current

GG

0284

Uint32 4

R W Milliamp

0 - 3000000

ECU Config

Voltage Regulator Primary

Underfrequency Knee

GG

0286

Uint32 4

R W Decihertz

400 - 700

Advertising