Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 219

Advertising
background image

9469300991 Rev A

213

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

AEM 3 Analog Input 4=339
AEM 3 Analog Input 5=340

AEM 3 Analog Input 6=341

AEM 3 Analog Input 7=342
AEM 3 Analog Input 8=343

AEM 3 RTD Input 1=344
AEM 3 RTD Input 2=345

AEM 3 RTD Input 3=346
AEM 3 RTD Input 4=347

AEM 3 RTD Input 5=348

AEM 3 RTD Input 6=349
AEM 3 RTD Input 7=350

AEM 3 RTD Input 8=351
AEM 3 TC Input 1=352

AEM 3 TC Input 2=353
AEM 4 Analog Input 1=354

AEM 4 Analog Input 2=355

AEM 4 Analog Input 3=356
AEM 4 Analog Input 4=357

AEM 4 Analog Input 5=358
AEM 4 Analog Input 6=359

AEM 4 Analog Input 7=360
AEM 4 Analog Input 8=361

AEM 4 RTD Input 1=362

AEM 4 RTD Input 2=363
AEM 4 RTD Input 3=364

AEM 4 RTD Input 4=365
AEM 4 RTD Input 5=366

AEM 4 RTD Input 6=367
AEM 4 RTD Input 7=368

AEM 4 RTD Input 8=369
AEM 4 TC Input 1=370

AEM 4 TC Input 2=371

AVR Output=372
GOV Output=373

LS Output=374

Config Protection 3

Hysteresis

GG

24838

Float

4

R W Percent

0 - 100

Config Protection 3

Arming Delay

GG

24840

Float

4

R W Second

0 - 300

Config Protection 3

Threshold 1 Type

GG

24842

Int32

4

R W n/a

Disabled=0
Over=1

Under=2

Config Protection 3

Threshold 1 Pickup

GG

24844

Float

4

R W n/a

-999999 - 999999

Config Protection 3

Threshold 1 Activation Delay

GG

24846

Float

4

R W Second

0 - 300

Config Protection 3

Threshold 1 Alarm Configuration GG

24848

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Config Protection 3

Threshold 2 Type

GG

24850

Int32

4

R W n/a

Disabled=0

Over=1
Under=2

Config Protection 3

Threshold 2 Pickup

GG

24858

Float

4

R W n/a

-999999 - 999999

Config Protection 3

Threshold 2 Activation Delay

GG

24860

Float

4

R W Second

0 - 300

Config Protection 3

Threshold 2 Alarm Configuration GG

24862

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Config Protection 3

Threshold 3 Type

GG

24864

Int32

4

R W n/a

Disabled=0
Over=1

Under=2

Config Protection 3

Threshold 3 Pickup

GG

24866

Float

4

R W n/a

-999999 - 999999

Config Protection 3

Threshold 3 Activation Delay

GG

24868

Float

4

R W Second

0 - 300

Config Protection 3

Threshold 3 Alarm Configuration GG

24870

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Config Protection 3

Threshold 4 Type

GG

24872

Int32

4

R W n/a

Disabled=0

Over=1
Under=2

Config Protection 3

Threshold 4 Pickup

GG

24874

Float

4

R W n/a

-999999 - 999999

Config Protection 3

Threshold 4 Activation Delay

GG

24876

Float

4

R W Second

0 - 300

Config Protection 3

Threshold 4 Alarm Configuration GG

24878

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Config Protection 3

Low-Line Scale Current

GG

24880

Float

4

R W n/a

0.001 - 3

Config Protection 3

Low-Line Scale Voltage

GG

24882

Float

4

R W n/a

0.001 - 3

Config Protection 3

Label

GG

24884

String 16

R W n/a

0 - 16

Config Protection 4

Parameter Selection

GG

24886

Int32

4

R W n/a

No Parameter=0
Oil Pressure=1

Coolant Temp=2
Battery Volts=3

RPM=4

Fuel Level=5
Gen Hz=6

Advertising