Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

Contact Input 3

Contact Recognition

GG

0432

Uint32 4

R W n/a

Always=0
Engine Running=1

Contact Input 3

Alarm Configuration

GG

0434

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Contact Input 3

Activation Delay

GG

0436

Uint32 4

R W Second

0 - 300

Contact Input 4

Contact Recognition

GG

0438

Uint32 4

R W n/a

Always=0
Engine Running=1

Contact Input 4

Alarm Configuration

GG

0440

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1

Alarm=2

Contact Input 4

Activation Delay

GG

0442

Uint32 4

R W Second

0 - 300

Contact Input 5

Contact Recognition

GG

0444

Uint32 4

R W n/a

Always=0

Engine Running=1

Contact Input 5

Alarm Configuration

GG

0446

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Contact Input 5

Activation Delay

GG

0448

Uint32 4

R W Second

0 - 300

Contact Input 6

Contact Recognition

GG

0450

Uint32 4

R W n/a

Always=0
Engine Running=1

Contact Input 6

Alarm Configuration

GG

0452

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Contact Input 6

Activation Delay

GG

0454

Uint32 4

R W Second

0 - 300

Contact Input 7

Contact Recognition

GG

0456

Uint32 4

R W n/a

Always=0
Engine Running=1

Contact Input 7

Alarm Configuration

GG

0458

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1

Alarm=2

Contact Input 7

Activation Delay

GG

0460

Uint32 4

R W Second

0 - 300

Contact Input 8

Contact Recognition

GG

0462

Uint32 4

R W n/a

Always=0

Engine Running=1

Contact Input 8

Alarm Configuration

GG

0464

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Contact Input 8

Activation Delay

GG

0466

Uint32 4

R W Second

0 - 300

Contact Input 9

Contact Recognition

GG

0468

Uint32 4

R W n/a

Always=0
Engine Running=1

Contact Input 9

Alarm Configuration

GG

0470

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Contact Input 9

Activation Delay

GG

0472

Uint32 4

R W Second

0 - 300

Contact Input 10

Contact Recognition

GG

0474

Uint32 4

R W n/a

Always=0

Engine Running=1

Contact Input 10

Alarm Configuration

GG

0476

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Contact Input 10

Activation Delay

GG

0478

Uint32 4

R W Second

0 - 300

Contact Input 11

Contact Recognition

GG

0480

Uint32 4

R W n/a

Always=0

Engine Running=1

Contact Input 11

Alarm Configuration

GG

0482

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Contact Input 11

Activation Delay

GG

0484

Uint32 4

R W Second

0 - 300

Contact Input 12

Contact Recognition

GG

0486

Uint32 4

R W n/a

Always=0
Engine Running=1

Contact Input 12

Alarm Configuration

GG

0488

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Contact Input 12

Activation Delay

GG

0490

Uint32 4

R W Second

0 - 300

Contact Input 13

Contact Recognition

GG

0492

Uint32 4

R W n/a

Always=0

Engine Running=1

Contact Input 13

Alarm Configuration

GG

0494

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Contact Input 13

Activation Delay

GG

0496

Uint32 4

R W Second

0 - 300

Contact Input 14

Contact Recognition

GG

0498

Uint32 4

R W n/a

Always=0

Engine Running=1

Contact Input 14

Alarm Configuration

GG

0500

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Contact Input 14

Activation Delay

GG

0502

Uint32 4

R W Second

0 - 300

Contact Input 15

Contact Recognition

GG

0504

Uint32 4

R W n/a

Always=0
Engine Running=1

Contact Input 15

Alarm Configuration

GG

0506

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Contact Input 15

Activation Delay

GG

0508

Uint32 4

R W Second

0 - 300