Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 121

Advertising
background image

9469300991 Rev A

115

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

AEM 4 Remote Analog
Output 1

Out-of-Range Activation
Delay

GG

8562

Float

4

R W Second 0 - 300

AEM 4 Remote Analog
Output 1

Parameter Minimum

GG

8564

Float

4

R W n/a

-999999 - 999999

AEM 4 Remote Analog
Output 1

Parameter Maximum

GG

8566

Float

4

R W n/a

-999999 - 999999

AEM 4 Remote Analog
Output 1

Current Minimum

GG

8568

Float

4

R W Milliamp 4 - 20

AEM 4 Remote Analog

Output 1

Current Maximum

GG

8570

Float

4

R W Milliamp 4 - 20

AEM 4 Remote Analog

Output 1

Voltage Minimum

GG

8572

Float

4

R W Volt

0 - 10

AEM 4 Remote Analog

Output 1

Voltage Maximum

GG

8574

Float

4

R W Volt

0 - 10

AEM 4 Remote Analog

Output 1

Alarm Configuration

GG

8576

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

AEM 4 Remote Analog
Output 2

Parameter Selection

GG

8578

Int32

4

R W n/a

No Parameter=0
Oil Pressure=1

Coolant Temp=2
Battery Volts=3

RPM=4
Fuel Level=5

Gen Hz=6

Gen VAB=7
Gen VBC=8

Gen VCA=9
Gen Vavg LL=10

Gen VAN=11
Gen VBN=12

Gen VCN=13
Gen Vavg LN=14

Bus 1 Hz=15

Bus 1 VAB=16
Bus 1 VBC=17

Bus 1 VCA=18
Bus 1 Vavg LL=19

Bus 1 VA=20
Bus 1 VB=21

Bus 1 VC=22

Bus 1 Vavg LN=23
Bus 2 Hz=24

Bus 2 VAB=25
Bus 2 VBC=26

Bus 2 VCA=27
Bus 2 Vavg LL=28

Bus 2 VAN=29

Bus 2 VBN=30
Bus 2 VCN=31

Bus 2 Vavg LN=32
Gen PF=33

Bus 1 PF=34
Bus 2 PF=35

Gen Pos kWh=36
Gen Neg kWh=37

Bus 1 Pos kWh=38

Bus 1 Neg kWh=39
Bus 2 Pos kWh=40

Bus 2 Neg kWh=41
Gen IA=42

Gen IB=43
Gen IC=44

Gen I Avg=45

Bus 1 IA=46
Bus 1 IB=47

Bus 1 IC=48
Bus 1 Iavg=49

Bus 2 IAN=50
Bus 2 IBN=51

Bus 2 ICN=52

Bus 2 Iavg=53
IG=54

I Aux=55
Gen kW A=56

Gen kW B=57
Gen kW C=58

Gen kW Total=59

Bus 1 kW A=60
Bus 1 kW B=61

Bus 1 kW C=62
Bus 1 kW Total=63