Binary points – Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 27

Advertising
background image

9469300991 Rev A

21

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

CEM 4 Contact Input 9 Contact Recognition

GG

0744

Uint32 4

R W n/a

Always=0
Engine Running=1

CEM 4 Contact Input 9 Alarm Configuration

GG

0746

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

CEM 4 Contact Input 9 Activation Delay

GG

0748

Uint32 4

R W Second

0 - 300

CEM 4 Contact Input
10

Contact Recognition

GG

0750

Uint32 4

R W n/a

Always=0
Engine Running=1

CEM 4 Contact Input

10

Alarm Configuration

GG

0752

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1

Alarm=2

CEM 4 Contact Input
10

Activation Delay

GG

0754

Uint32 4

R W Second

0 - 300

Auto Config Detect

Enable

GG

0756

Uint32 4

R W n/a

Disabled=0
Enabled=1

Auto Config Detect

Single-Phase Detection Threshold

GG

0758

Float

4

R W Volt

0 - 480

Auto Config Detect

Single-Phase Detection Gen Connection

GG

0760

Uint32 4

R W n/a

AB=0

AC=1

Auto Config Detect

Low-Line Detection Threshold

GG

0762

Float

4

R W Volt

0 - 480

Binary Points

Name

Description

Register Bit Type Bytes R/W

Range

Scale Factor Override

Alternate Frequency Override

1000

0

Uint16 2

R

False=0 True=1

Reserved

1000

1

System Data

Logic 0

1000

2

Uint16 2

R

False=0 True=1

System Data

Logic 1

1000

3

Uint16 2

R

False=0 True=1

Alarms

Real-Time Clock Alarm

1000

4

Uint16 2

R

False=0 True=1

Alarms

Date/Time Set Alarm

1000

5

Uint16 2

R

False=0 True=1

Alarms

Firmware Change Alarm

1000

6

Uint16 2

R

False=0 True=1

Alarms

Frequency Out-of-Range Alarm

1000

7

Uint16 2

R

False=0 True=1

Alarms

Ethernet Link 1 Lost Alarm

1000

8

Uint16 2

R

False=0 True=1

Alarms

Ethernet Link 2 Lost Alarm

1000

9

Uint16 2

R

False=0 True=1

Alarms

USB COM Alarm

1000

10 Uint16 2

R

False=0 True=1

Alarms

IRIG Sync Lost Alarm

1000

11 Uint16 2

R

False=0 True=1

Alarms

Logic = None Alarm

1000

12 Uint16 2

R

False=0 True=1

Alarms

No User Setting Alarm

1000

13 Uint16 2

R

False=0 True=1

Alarms

NTP Sync Lost Alarm

1000

14 Uint16 2

R

False=0 True=1

Alarms

uP Reset Alarm

1000

15 Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 1

1001

0

Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 2

1001

1

Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 3

1001

2

Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 4

1001

3

Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 5

1001

4

Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 6

1001

5

Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 7

1001

6

Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 8

1001

7

Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 9

1001

8

Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 10

1001

9

Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 11

1001

10 Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 12

1001

11 Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 13

1001

12 Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 14

1001

13 Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 15

1001

14 Uint16 2

R

False=0 True=1

Alarms

Programmable Alarm 16

1001

15 Uint16 2

R

False=0 True=1

Alarms

Unsupported Number of AEMs

1002

0

Uint16 2

R

False=0 True=1

Alarms

Unsupported Number of CEMs

1002

1

Uint16 2

R

False=0 True=1

Alarms

Logic Alarm

1002

2

Uint16 2

R

False=0 True=1

Alarms

Logic Pre-Alarm

1002

3

Uint16 2

R

False=0 True=1

Alarms

Global Sender Fail Alarm

1002

4

Uint16 2

R

False=0 True=1

Alarms

Clock Not Set Alarm

1002

5

Uint16 2

R

False=0 True=1

Alarms

Clock Battery Low Alarm

1002

6

Uint16 2

R

False=0 True=1

Alarm Report

Alarm Output

1002

7

Uint16 2

R

False=0 True=1

Pre-Alarm Report

Alarm Output

1002

8

Uint16 2

R

False=0 True=1

Contact Outputs

Output 1

1002

9

Uint16 2

R

False=0 True=1

Contact Outputs

Output 2

1002

10 Uint16 2

R

False=0 True=1

Contact Outputs

Output 3

1002

11 Uint16 2

R

False=0 True=1

Contact Outputs

Output 4

1002

12 Uint16 2

R

False=0 True=1

Contact Outputs

Output 5

1002

13 Uint16 2

R

False=0 True=1

Contact Outputs

Output 6

1002

14 Uint16 2

R

False=0 True=1

Contact Outputs

Output 7

1002

15 Uint16 2

R

False=0 True=1

Contact Outputs

Output 8

1003

0

Uint16 2

R

False=0 True=1

Contact Outputs

Output 9

1003

1

Uint16 2

R

False=0 True=1

Contact Outputs

Output 10

1003

2

Uint16 2

R

False=0 True=1

Advertising