Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

Coolant Temperature
Protection

High Coolant TempPre-Alarm
Threshold

GG

24706

Float

4

R W Deg F

100 - 280

Coolant Temperature
Protection

Low Coolant Temp Pre-Alarm
Threshold

GG

24708

Float

4

R W Deg F

35 - 151

Coolant Temperature
Protection

High Coolant Temp Arming
Delay

GG

24710

Float

4

R W Millisecond 0 - 150000

Fuel Level Protection

Low Fuel Alarm Mode

GG

24712

Uint32 4

R W n/a

No=0
Yes=1

Fuel Level Protection

LowFuelPreAlarmMode

GG

24714

Uint32 4

R W n/a

No=0

Yes=1

Fuel Level Protection

High Fuel Pre-Alarm Mode

GG

24716

Uint32 4

R W n/a

No=0

Yes=1

Fuel Level Protection

Low Fuel Alarm Threshold

GG

24718

Float

4

R W Percent

0 - 100

Fuel Level Protection

Low Fuel Pre-Alarm Threshold

GG

24720

Float

4

R W Percent

10 - 100

Fuel Level Protection

High Fuel Pre-Alarm Threshold

GG

24722

Float

4

R W Percent

0 - 150

Fuel Level Protection

Low Fuel Alarm Activation Delay GG

24724

Float

4

R W Millisecond 0 - 30000

Fuel Level Protection

High Fuel Pre-Alarm Activation

Delay

GG

24726

Float

4

R W Millisecond 0 - 30000

Overspeed Protection

Overspeed Mode

GG

24728

Uint32 4

R W n/a

No=0

Yes=1

Overspeed Protection

Overspeed Threshold

GG

24730

Float

4

R W Percent

105 - 140

Overspeed Protection

Overspeed Activation Delay

GG

24732

Float

4

R W Millisecond 0 - 500

Coolant Level
Protection

Low Coolant Level Alarm Mode

GG

24734

Uint32 4

R W n/a

No=0
Yes=1

Coolant Level
Protection

Low Coolant Level Pre-Alarm
Mode

GG

24736

Uint32 4

R W n/a

No=0
Yes=1

Coolant Level
Protection

Low Coolant Level Alarm
Threshold

GG

24738

Float

4

R W Percent

1 - 99

Coolant Level
Protection

Low Coolant Level Pre-Alarm
Threshold

GG

24740

Float

4

R W Percent

1 - 99

Config Protection 1

Parameter Selection

GG

24742

Int32

4

R W n/a

No Parameter=0

Oil Pressure=1

Coolant Temp=2
Battery Volts=3

RPM=4
Fuel Level=5

Gen Hz=6
Gen VAB=7

Gen VBC=8

Gen VCA=9
Gen Vavg LL=10

Gen VAN=11
Gen VBN=12

Gen VCN=13
Gen Vavg LN=14

Bus 1 Hz=15
Bus 1 VAB=16

Bus 1 VBC=17

Bus 1 VCA=18
Bus 1 Vavg LL=19

Bus 1 VA=20
Bus 1 VB=21

Bus 1 VC=22
Bus 1 Vavg LN=23

Bus 2 Hz=24

Bus 2 VAB=25
Bus 2 VBC=26

Bus 2 VCA=27
Bus 2 Vavg LL=28

Bus 2 VAN=29
Bus 2 VBN=30

Bus 2 VCN=31

Bus 2 Vavg LN=32
Gen PF=33

Bus 1 PF=34
Bus 2 PF=35

Gen Pos kWh=36
Gen Neg kWh=37

Bus 1 Pos kWh=38
Bus 1 Neg kWh=39

Bus 2 Pos kWh=40

Bus 2 Neg kWh=41
Gen IA=42

Gen IB=43
Gen IC=44

Gen I Avg=45
Bus 1 IA=46

Bus 1 IB=47

Bus 1 IC=48
Bus 1 Iavg=49

Advertising