Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 253

Advertising
background image

9469300991 Rev A

247

DGC-2020HD Modbus

™ Protocol

Legacy Register Table

Register

Description

Type

Units

Scaling

Factor

R/W

Range

44818-19

MTU Pre-Alarm Metering

Int32

n/a

n/a

R

Bit 0 = Low Storage Tank
Bit 1 = High Storage Tank

Bit 2 = Low Day Tank
Bit 3 = High Day Tank

Bit 4 = Alternator Winding Temp

Bit 5 = Idle Speed Low
Bit 6 = Run Up Speed Low

Bit 7 = Start Speed Low
Bit 8 = Priming Fault

Bit 9 = Low Charge Air Coolant Level
Bit 10 = High Fuel Temp.

Bit 11 = High Exhaust Temp. B
Bit 12 = High Exhaust Temp. A

Bit 13 = Low ECU Supply Voltage

Bit 14 = Engine Speed Too Low
Bit 15 = High Voltage Supply

Bit 16 = Low Voltage Supply
Bit 17 = Speed Demand Fail

Bit 18 = ECU Faulty
Bit 19 = Combined Yellow

Bit 20 = Low Oil Press.

Bit 21 = Low Fuel Delivery Press.
Bit 22 = Low Charge Air Press.

Bit 23 = Low Coolant Level
Bit 24 = Low Fuel Rail Press.

Bit 25 = High Fuel Rail Press.
Bit 26 = Shutdown Override

Bit 27 = High Coolant Temp.

Bit 28 = High Charge Air Temp.
Bit 29 = High Intercooler Temp.

Bit 30 = High Oil Temp.
Bit 31 = High ECU Temp.

44820-21

Sender Fail Alarm Metering

Int32

n/a

n/a

R

Bit 0 = Not Used
Bit 1 = Not Used

Bit 2 = Not Used
Bit 3 = Not Used

Bit 4 = Not Used
Bit 5 = Not Used

Bit 6 = Not Used

Bit 7 = Not Used
Bit 8 = Not Used

Bit 9 = Not Used
Bit 10 = Not Used

Bit 11 = Not Used
Bit 12 = Not Used

Bit 13 = Not Used

Bit 14 = Not Used
Bit 15 = Not Used

Bit 16 = Not Used
Bit 17 = Not Used

Bit 18 = Not Used
Bit 19 = Not Used

Bit 20 = Not Used

Bit 21 = Not Used
Bit 22 = Not Used

Bit 23 = Not Used
Bit 24 = Not Used

Bit 25 = Not Used
Bit 26 = Not Used

Bit 27 = Generator Voltage
Bit 28 = Fuel Level

Bit 29 = Coolant Temp

Bit 30 = Oil Pressure
Bit 31 = Speed

44822-26

Reserved