Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 25

Advertising
background image

9469300991 Rev A

19

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

CEM 2 Contact Input 3 Contact Recognition

GG

0588

Uint32 4

R W n/a

Always=0
Engine Running=1

CEM 2 Contact Input 3 Alarm Configuration

GG

0590

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

CEM 2 Contact Input 3 Activation Delay

GG

0592

Uint32 4

R W Second

0 - 300

CEM 2 Contact Input 4 Contact Recognition

GG

0594

Uint32 4

R W n/a

Always=0
Engine Running=1

CEM 2 Contact Input 4 Alarm Configuration

GG

0596

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1

Alarm=2

CEM 2 Contact Input 4 Activation Delay

GG

0598

Uint32 4

R W Second

0 - 300

CEM 2 Contact Input 5 Contact Recognition

GG

0600

Uint32 4

R W n/a

Always=0

Engine Running=1

CEM 2 Contact Input 5 Alarm Configuration

GG

0602

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

CEM 2 Contact Input 5 Activation Delay

GG

0604

Uint32 4

R W Second

0 - 300

CEM 2 Contact Input 6 Contact Recognition

GG

0606

Uint32 4

R W n/a

Always=0
Engine Running=1

CEM 2 Contact Input 6 Alarm Configuration

GG

0608

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

CEM 2 Contact Input 6 Activation Delay

GG

0610

Uint32 4

R W Second

0 - 300

CEM 2 Contact Input 7 Contact Recognition

GG

0612

Uint32 4

R W n/a

Always=0
Engine Running=1

CEM 2 Contact Input 7 Alarm Configuration

GG

0614

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1

Alarm=2

CEM 2 Contact Input 7 Activation Delay

GG

0616

Uint32 4

R W Second

0 - 300

CEM 2 Contact Input 8 Contact Recognition

GG

0618

Uint32 4

R W n/a

Always=0

Engine Running=1

CEM 2 Contact Input 8 Alarm Configuration

GG

0620

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

CEM 2 Contact Input 8 Activation Delay

GG

0622

Uint32 4

R W Second

0 - 300

CEM 2 Contact Input 9 Contact Recognition

GG

0624

Uint32 4

R W n/a

Always=0
Engine Running=1

CEM 2 Contact Input 9 Alarm Configuration

GG

0626

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

CEM 2 Contact Input 9 Activation Delay

GG

0628

Uint32 4

R W Second

0 - 300

CEM 2 Contact Input

10

Contact Recognition

GG

0630

Uint32 4

R W n/a

Always=0

Engine Running=1

CEM 2 Contact Input

10

Alarm Configuration

GG

0632

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

CEM 2 Contact Input
10

Activation Delay

GG

0634

Uint32 4

R W Second

0 - 300

CEM 3 Contact Input 1 Contact Recognition

GG

0636

Uint32 4

R W n/a

Always=0
Engine Running=1

CEM 3 Contact Input 1 Alarm Configuration

GG

0638

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

CEM 3 Contact Input 1 Activation Delay

GG

0640

Uint32 4

R W Second

0 - 300

CEM 3 Contact Input 2 Contact Recognition

GG

0642

Uint32 4

R W n/a

Always=0

Engine Running=1

CEM 3 Contact Input 2 Alarm Configuration

GG

0644

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

CEM 3 Contact Input 2 Activation Delay

GG

0646

Uint32 4

R W Second

0 - 300

CEM 3 Contact Input 3 Contact Recognition

GG

0648

Uint32 4

R W n/a

Always=0

Engine Running=1

CEM 3 Contact Input 3 Alarm Configuration

GG

0650

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

CEM 3 Contact Input 3 Activation Delay

GG

0652

Uint32 4

R W Second

0 - 300

CEM 3 Contact Input 4 Contact Recognition

GG

0654

Uint32 4

R W n/a

Always=0
Engine Running=1

CEM 3 Contact Input 4 Alarm Configuration

GG

0656

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1

Alarm=2

CEM 3 Contact Input 4 Activation Delay

GG

0658

Uint32 4

R W Second

0 - 300

CEM 3 Contact Input 5 Contact Recognition

GG

0660

Uint32 4

R W n/a

Always=0

Engine Running=1

CEM 3 Contact Input 5 Alarm Configuration

GG

0662

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

CEM 3 Contact Input 5 Activation Delay

GG

0664

Uint32 4

R W Second

0 - 300

Advertising