Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 151

Advertising
background image

9469300991 Rev A

145

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

59P-4

Alarm Configuration

SG1 3P 21004

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

59P-4

Low-Line Scale

SG1 3P 21006

Float

4

R W n/a

0.001 - 3

59P-4

Mode

SG2 1P 21008

Uint32 4

R W n/a

Disabled=0
Enabled=1

59P-4

Source

SG2 1P 21010

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

59P-4

Pickup

SG2 1P 21012

Float

4

R W Volt

1 - 576

59P-4

Time Delay

SG2 1P 21014

Float

4

R W Millisecond 0 - 600000

59P-4

Alarm Configuration

SG2 1P 21016

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

59P-4

Low-Line Scale

SG2 1P 21018

Float

4

R W n/a

0.001 - 3

59P-4

Mode

SG2 3P 21020

Uint32 4

R W n/a

Disabled=0

Enabled=1

59P-4

Source

SG2 3P 21022

Uint32 4

R W n/a

Gen=0

Bus 1=1
Bus 2=2

59P-4

Pickup

SG2 3P 21024

Float

4

R W Volt

1 - 576

59P-4

Time Delay

SG2 3P 21026

Float

4

R W Millisecond 0 - 600000

59P-4

Alarm Configuration

SG2 3P 21028

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1

Alarm=2

59P-4

Low-Line Scale

SG2 3P 21030

Float

4

R W n/a

0.001 - 3

59P-4

Mode

SG3 1P 21032

Uint32 4

R W n/a

Disabled=0

Enabled=1

59P-4

Source

SG3 1P 21034

Uint32 4

R W n/a

Gen=0

Bus 1=1
Bus 2=2

59P-4

Pickup

SG3 1P 21036

Float

4

R W Volt

1 - 576

59P-4

Time Delay

SG3 1P 21038

Float

4

R W Millisecond 0 - 600000

59P-4

Alarm Configuration

SG3 1P 21040

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

59P-4

Low-Line Scale

SG3 1P 21042

Float

4

R W n/a

0.001 - 3

59P-4

Mode

SG3 3P 21044

Uint32 4

R W n/a

Disabled=0
Enabled=1

59P-4

Source

SG3 3P 21046

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

59P-4

Pickup

SG3 3P 21048

Float

4

R W Volt

1 - 576

59P-4

Time Delay

SG3 3P 21050

Float

4

R W Millisecond 0 - 600000

59P-4

Alarm Configuration

SG3 3P 21052

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

59P-4

Low-Line Scale

SG3 3P 21054

Float

4

R W n/a

0.001 - 3

59P-5

Mode

SG0 1P 21056

Uint32 4

R W n/a

Disabled=0
Enabled=1

59P-5

Source

SG0 1P 21058

Uint32 4

R W n/a

Gen=0

Bus 1=1

Bus 2=2

59P-5

Pickup

SG0 1P 21060

Float

4

R W Volt

1 - 576

59P-5

Time Delay

SG0 1P 21062

Float

4

R W Millisecond 0 - 600000

59P-5

Alarm Configuration

SG0 1P 21064

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

59P-5

Low-Line Scale

SG0 1P 21066

Float

4

R W n/a

0.001 - 3

59P-5

Mode

SG0 3P 21068

Uint32 4

R W n/a

Disabled=0

Enabled=1

59P-5

Source

SG0 3P 21070

Uint32 4

R W n/a

Gen=0

Bus 1=1
Bus 2=2

59P-5

Pickup

SG0 3P 21072

Float

4

R W Volt

1 - 576

59P-5

Time Delay

SG0 3P 21074

Float

4

R W Millisecond 0 - 600000

59P-5

Alarm Configuration

SG0 3P 21076

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

59P-5

Low-Line Scale

SG0 3P 21078

Float

4

R W n/a

0.001 - 3

59P-5

Mode

SG1 1P 21080

Uint32 4

R W n/a

Disabled=0

Enabled=1

59P-5

Source

SG1 1P 21082

Uint32 4

R W n/a

Gen=0

Bus 1=1
Bus 2=2

59P-5

Pickup

SG1 1P 21084

Float

4

R W Volt

1 - 576

59P-5

Time Delay

SG1 1P 21086

Float

4

R W Millisecond 0 - 600000

Advertising