Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 57

Advertising
background image

9469300991 Rev A

51

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group

Register

Type

Bytes R/W

Unit

Range

Bias Control

GOV Outer Controller Output

GG

2112

Float

4

R W n/a

n/a

Bias Control

GOV Inner Controller Error

GG

2114

Float

4

R W n/a

n/a

Bias Control

GOV Outer Controller Error

GG

2116

Float

4

R W n/a

n/a

Bias Control

Speed Trim Setpoint

GG

2118

Float

4

R W Hertz

47 - 100

Bias Control

var Control Enabled

GG

2120

Uint32

4

R W n/a

Disabled=0

Enabled=1

Bias Control

kvar Load Rate

GG

2122

Float

4

R W Percent

0 - 100

Bias Control

kW Setpoint Source

GG

2124

Uint32

4

R W n/a

User Setting=0

Local Analog Input 1=1

Local Analog Input 2=2
Local Analog Input 3=3

Local Analog Input 4=4
AEM 1 Analog Input 1=5

AEM 1 Analog Input 2=6
AEM 1 Analog Input 3=7

AEM 1 Analog Input 4=8
AEM 1 Analog Input 5=9

AEM 1 Analog Input 6=10

AEM 1 Analog Input 7=11
AEM 1 Analog Input 8=12

AEM 2 Analog Input 1=13
AEM 2 Analog Input 2=14

AEM 2 Analog Input 3=15
AEM 2 Analog Input 4=16

AEM 2 Analog Input 5=17

AEM 2 Analog Input 6=18
AEM 2 Analog Input 7=19

AEM 2 Analog Input 8=20
AEM 3 Analog Input 1=21

AEM 3 Analog Input 2=22
AEM 3 Analog Input 3=23

AEM 3 Analog Input 4=24

AEM 3 Analog Input 5=25
AEM 3 Analog Input 6=26

AEM 3 Analog Input 7=27
AEM 3 Analog Input 8=28

AEM 4 Analog Input 1=29
AEM 4 Analog Input 2=30

AEM 4 Analog Input 3=31

AEM 4 Analog Input 4=32
AEM 4 Analog Input 5=33

AEM 4 Analog Input 6=34
AEM 4 Analog Input 7=35

AEM 4 Analog Input 8=36

Bias Control

kvar Setpoint Source

GG

2126

Uint32

4

R W n/a

User Setting=0

Local Analog Input 1=1
Local Analog Input 2=2

Local Analog Input 3=3
Local Analog Input 4=4

AEM 1 Analog Input 1=5
AEM 1 Analog Input 2=6

AEM 1 Analog Input 3=7

AEM 1 Analog Input 4=8
AEM 1 Analog Input 5=9

AEM 1 Analog Input 6=10
AEM 1 Analog Input 7=11

AEM 1 Analog Input 8=12
AEM 2 Analog Input 1=13

AEM 2 Analog Input 2=14

AEM 2 Analog Input 3=15
AEM 2 Analog Input 4=16

AEM 2 Analog Input 5=17
AEM 2 Analog Input 6=18

AEM 2 Analog Input 7=19
AEM 2 Analog Input 8=20

AEM 3 Analog Input 1=21

AEM 3 Analog Input 2=22
AEM 3 Analog Input 3=23

AEM 3 Analog Input 4=24
AEM 3 Analog Input 5=25

AEM 3 Analog Input 6=26
AEM 3 Analog Input 7=27

AEM 3 Analog Input 8=28

AEM 4 Analog Input 1=29
AEM 4 Analog Input 2=30

AEM 4 Analog Input 3=31
AEM 4 Analog Input 4=32

AEM 4 Analog Input 5=33
AEM 4 Analog Input 6=34

AEM 4 Analog Input 7=35
AEM 4 Analog Input 8=36