Control – Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 244

Advertising
background image

238

9469300991 Rev A

Legacy Register Table

DGC-2020HD Modbus

™ Protocol

Register

Description

Type

Units

Scaling Factor

R/W

Range

43656

Not In Auto Horn Enable

Uint32

n/a

n/a

RW

0 = Disable

1 = Enable

43658

Clock Not Set Warning Enable

Uint32

n/a

n/a

RW

0 = Disable

1 = Enable

43660

Alternate Frequency

Int32

Hertz

Centi

RW

1000 - 9000

43662

Generator System Type

Int32

n/a

n/a

RW

0 = Single Generator

1 = Multiple Generator

43664

Gen CT Low Line Scale Factor

Float

n/a

n/a

RW

0.001 - 3

43666

Metric Pressure Units

Int32

n/a

n/a

RW

0 = Bar
1 = kPa

43668

System Units

Int32

n/a

n/a

RW

0 = English
1 = Metric

43674

RPM Bandwidth Data

Int32

n/a

n/a

RW

0 - 1000

43676

Number Flywheel Teeth

Uint32

n/a

Deci

RW

10 - 5000

43678

Phase Rotation

Int32

n/a

n/a

RW

0 = ACB
1 = ABC

43680

Restart Delay

Int32

Second

n/a

RW

0 - 120

43682

Configured Bus Connection

Uint32

n/a

n/a

RW

0 = Single-Phase
1 = Three-Phase

43684

Fuel Level Source

Int32

n/a

n/a

RW

1 – 9

43686

Fuel Level Percent Max

Int32

n/a

n/a

RW

0 – 150

43688

Fuel Level Percent Min

Int32

n/a

n/a

RW

0 – 150

Control

Register

Description

Type Units

Scaling

Factor

R/W

Range

43750

Emergency Stop: Writing a 1 will toggle emergency stop from off to on. Writing
a 1 again will toggle emergency stop from on to off

Int32 n/a

n/a

RW 1 = Toggle On/Off

43752

Remote Start

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43754

Remote Stop

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43756

Run Mode

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43758

Off Mode

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43760

Auto Mode

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43762

Alarm Reset

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43764

Gen Breaker Open

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43766

Gen Breaker Close

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43768

Mains Breaker Open

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43770

Mains Breaker Close

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43772

Reserved

43774

Virtual Input 1 Close

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43776

Virtual Input 1 Open

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43778

Virtual Input 2 Close

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43780

Virtual Input 2 Open

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43782

Virtual Input 3 Close

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43784

Virtual Input 3 Open

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43786

Virtual Input 4 Close

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43788

Virtual Input 4 Open

Int32 n/a

n/a

RW 0 = Disable

1 = Enable

43790

ESTOP Latch Status

Int32 n/a

n/a

R

0 = Disabled

1 = Enabled

43792

Gen Breaker Open

Int32 n/a

n/a

RW 1 = Operate (non-

latching)

43794

Gen Breaker Close

Int32 n/a

n/a

RW 1 = Operate (non-

latching)

43796

Mains Breaker Open

Int32 n/a

n/a

RW 1 = Operate (non-

latching)

43798

Mains Breaker Close

Int32 n/a

n/a

RW 1 = Operate (non-

latching)