Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 191

Advertising
background image

9469300991 Rev A

185

DGC-2020HD Modbus

™ Protocol

Default Register Table

Name

Description

Group Register Type Bytes R/W

Unit

Range

51-3

Mode

SG3 3P 23708

Uint32 4

R W n/a

Disabled=0
IA=1

IB=2

IC=3
Imax=4

3I0=5
I2=6

IG=7
I1=8

51-3

Source

SG3 3P 23710

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

51-3

Pickup

SG3 3P 23712

Float

4

R W Amp

0.9 - 7.75

51-3

Curve Index

SG3 3P 23714

Uint32 4

R W n/a

S1=0
S2=1

L1=2
L2=3

D=4
M=5

I1=6
I2=7

V1=8

V2=9
E1=10

E2=11
A=12

B=13
C=14

G=15

F=16
46=17

P=18

51-3

Direction

SG3 3P 23716

Uint32 4

R W n/a

Forward=0

Reverse=1
Non-Directional=2

51-3

Use Instantaneous Reset

SG3 3P 23718

Uint32 4

R W n/a

Integrating=0

Instantaneous=1

51-3

Constant TD

SG3 3P 23720

Float

4

R W n/a

0 - 9.9

51-3

Constant A

SG3 3P 23722

Float

4

R W n/a

0 - 600

51-3

Constant B

SG3 3P 23724

Float

4

R W n/a

0 - 25

51-3

Constant C

SG3 3P 23726

Float

4

R W n/a

0 - 1

51-3

Constant N

SG3 3P 23728

Float

4

R W n/a

0.5 - 2.5

51-3

Constant R

SG3 3P 23730

Float

4

R W n/a

0 - 30

51-3

Voltage Restraint Setpoint

SG3 3P 23732

Float

4

R W Volt

30 - 250

51-3

Voltage Restraint Mode

SG3 3P 23734

Uint32 4

R W n/a

Disabled=0
Control=1

Restraint=2

51-3

Alarm Configuration

SG3 3P 23736

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

51-3

Low-Line Scale

SG3 3P 23738

Float

4

R W n/a

0.001 - 3

51-3

Voltage Restraint Source

SG3 3P 23740

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

51-3

Constant Q

SG3 3P 23742

Float

4

R W n/a

0.1 - 10

51-4

Mode

SG0 1P 23744

Uint32 4

R W n/a

Disabled=0
IA=1

IB=2
IC=3

Imax=4
3I0=5

I2=6

IG=7
I1=8

51-4

Source

SG0 1P 23746

Uint32 4

R W n/a

Gen=0

Bus 1=1

Bus 2=2

51-4

Pickup

SG0 1P 23748

Float

4

R W Amp

0.9 - 7.75