Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 162

Advertising
background image

156

9469300991 Rev A

Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Group Register Type Bytes R/W

Unit

Range

81-8

Source

SG2

21898

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

81-8

Pickup

SG2

21900

Float

4

R W Hertz

37.5 - 66

81-8

Time Delay

SG2

21902

Float

4

R W Millisecond 0 - 600000

81-8

Voltage Inhibit

SG2

21904

Float

4

R W Percent

1 - 100

81-8

Alarm Configuration

SG2

21906

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

81-8

Mode

SG3

21908

Uint32 4

R W n/a

Disabled=0
Over=1

Under=2

81-8

Source

SG3

21910

Uint32 4

R W n/a

Gen=0

Bus 1=1
Bus 2=2

81-8

Pickup

SG3

21912

Float

4

R W Hertz

37.5 - 66

81-8

Time Delay

SG3

21914

Float

4

R W Millisecond 0 - 600000

81-8

Voltage Inhibit

SG3

21916

Float

4

R W Percent

1 - 100

81-8

Alarm Configuration

SG3

21918

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

40Q-1

Mode

SG0 1P 21920

Uint32 4

R W n/a

Disabled=0

Enabled=1

40Q-1

Pickup

SG0 1P 21922

Float

4

R W Percent

-150 - 0

40Q-1

Time Delay

SG0 1P 21924

Float

4

R W Millisecond 0 - 600000

40Q-1

Source

SG0 1P 21926

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

40Q-1

Alarm Configuration

SG0 1P 21928

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

40Q-1

Low-Line Scale

SG0 1P 21930

Float

4

R W n/a

0.001 - 3

40Q-1

Mode

SG0 3P 21932

Uint32 4

R W n/a

Disabled=0
Enabled=1

40Q-1

Pickup

SG0 3P 21934

Float

4

R W Percent

-150 - 0

40Q-1

Time Delay

SG0 3P 21936

Float

4

R W Millisecond 0 - 600000

40Q-1

Source

SG0 3P 21938

Uint32 4

R W n/a

Gen=0

Bus 1=1
Bus 2=2

40Q-1

Alarm Configuration

SG0 3P 21940

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

40Q-1

Low-Line Scale

SG0 3P 21942

Float

4

R W n/a

0.001 - 3

40Q-1

Mode

SG1 1P 21944

Uint32 4

R W n/a

Disabled=0
Enabled=1

40Q-1

Pickup

SG1 1P 21946

Float

4

R W Percent

-150 - 0

40Q-1

Time Delay

SG1 1P 21948

Float

4

R W Millisecond 0 - 600000

40Q-1

Source

SG1 1P 21950

Uint32 4

R W n/a

Gen=0

Bus 1=1
Bus 2=2

40Q-1

Alarm Configuration

SG1 1P 21952

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1

Alarm=2

40Q-1

Low-Line Scale

SG1 1P 21954

Float

4

R W n/a

0.001 - 3

40Q-1

Mode

SG1 3P 21956

Uint32 4

R W n/a

Disabled=0

Enabled=1

40Q-1

Pickup

SG1 3P 21958

Float

4

R W Percent

-150 - 0

40Q-1

Time Delay

SG1 3P 21960

Float

4

R W Millisecond 0 - 600000

40Q-1

Source

SG1 3P 21962

Uint32 4

R W n/a

Gen=0
Bus 1=1

Bus 2=2

40Q-1

Alarm Configuration

SG1 3P 21964

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

40Q-1

Low-Line Scale

SG1 3P 21966

Float

4

R W n/a

0.001 - 3

40Q-1

Mode

SG2 1P 21968

Uint32 4

R W n/a

Disabled=0

Enabled=1

40Q-1

Pickup

SG2 1P 21970

Float

4

R W Percent

-150 - 0

40Q-1

Time Delay

SG2 1P 21972

Float

4

R W Millisecond 0 - 600000

40Q-1

Source

SG2 1P 21974

Uint32 4

R W n/a

Gen=0

Bus 1=1

Bus 2=2

40Q-1

Alarm Configuration

SG2 1P 21976

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

40Q-1

Low-Line Scale

SG2 1P 21978

Float

4

R W n/a

0.001 - 3

40Q-1

Mode

SG2 3P 21980

Uint32 4

R W n/a

Disabled=0
Enabled=1

Advertising