9469300991 Rev A

305

DGC-2020HD Modbus

™ Protocol

Legacy Register Table

Register

Description

Type

Units

Scaling

Factor

R/W

Range

46906

ATS Contact Input

Int32

n/a

n/a

RW -1 = None

0 = Input 1

1 = Input 2
2 = Input 3

3 = Input 4

4 = Input 5
5 = Input 6

6 = Input 7
7 = Input 8

8 = Input 9
9 = Input 10

10 = Input 11
11 = Input 12

12 = Input 13

13 = Input 14
14 = Input 15

15 = Input 16

46908

ATS Time Delay

Int32

Second

n/a

RW 0 – 300

46910

ATS Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46912

Battle Override Contact Input

Int32

n/a

n/a

RW -1 = None

0 = Input 1

1 = Input 2
2 = Input 3

3 = Input 4
4 = Input 5

5 = Input 6
6 = Input 7

7 = Input 8

8 = Input 9
9 = Input 10

10 = Input 11
11 = Input 12

12 = Input 13
13 = Input 14

14 = Input 15

15 = Input 16

46914

Battle Override Time Delay

Int32

Second

n/a

RW 0 – 300

46916

Battle Override Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46918

Low Coolant Level Contact Input

Int32

n/a

n/a

RW -1 = None

0 = Input 1
1 = Input 2

2 = Input 3

3 = Input 4
4 = Input 5

5 = Input 6
6 = Input 7

7 = Input 8
8 = Input 9

9 = Input 10

10 = Input 11
11 = Input 12

12 = Input 13
13 = Input 14

14 = Input 15
15 = Input 16

46920

Low Coolant Level Config Type

Int32

n/a

n/a

RW 0 = None

1 = Alarm

2 = Pre-Alarm

46922

Low Coolant Level Time Delay

Int32

Second

n/a

RW 0 – 300

46924

Low Coolant Level Engine Running Only

Int32

n/a

n/a

RW 0 = Always

1 = While Engine Running Only

46926

Battery Charge Failed Contact Input

Int32

n/a

n/a

RW -1 = None

0 = Input 1

1 = Input 2
2 = Input 3

3 = Input 4

4 = Input 5
5 = Input 6

6 = Input 7
7 = Input 8

8 = Input 9
9 = Input 10

10 = Input 11
11 = Input 12

12 = Input 13

13 = Input 14
14 = Input 15

15 = Input 16