Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 272

Advertising
background image

266

9469300991 Rev A

Legacy Register Table

DGC-2020HD Modbus

™ Protocol

Register

Description

Type

Units

Scaling

Factor

R/W

Range

45586-87

I/O Modules Connected

Uint32 n/a

n/a

R

Bit 0 = Not Used
Bit 1 = Not Used

Bit 2 = Not Used
Bit 3 = Not Used

Bit 4 = Not Used

Bit 5 = Not Used
Bit 6 = Not Used

Bit 7 = Not Used
Bit 8 = Not Used

Bit 9 = Not Used
Bit 10 = Not Used

Bit 11 = Not Used
Bit 12 = Not Used

Bit 13 = Not Used

Bit 14 = Not Used
Bit 15 = Not Used

Bit 16 = Not Used
Bit 17 = Not Used

Bit 18 = Not Used
Bit 19 = Not Used

Bit 20 = Not Used

Bit 21 = Not Used
Bit 22 = Not Used

Bit 23 = Not Used
Bit 24 = Not Used

Bit 25 = Not Used
Bit 26 = Not Used

Bit 27 = Not Used

Bit 28 = Not Used
Bit 29 = AEM Connected

Bit 30 = CEM Connected
Bit 31 = Not Used

45588

Max Vector Shift

Int32

n/a

Centi

R

0 - 100000

45590

Max DF/DT

Int32

n/a

Centi

R

0 - 100000

45592

Current DF/DT

Int32

n/a

Centi

R

0 - 100000

45594-95

Status Metering 2

Int32

n/a

n/a

R

Bit 0 = Not Used
Bit 1 = Not Used

Bit 2 = Not Used

Bit 3 = Not Used
Bit 4 = Not Used

Bit 5 = Not Used
Bit 6 = Not Used

Bit 7 = Not Used
Bit 8 = Not Used

Bit 9 = Not Used
Bit 10 = Not Used

Bit 11 = Not Used

Bit 12 = Not Used
Bit 13 = Not Used

Bit 14 = Not Used
Bit 15 = Not Used

Bit 16 = Bus Reverse Rotation
Bit 17 = Bus Forward Rotation

Bit 18 = Gen Reverse Rotation

Bit 19 = Gen Forward Rotation
Bit 20 = Closed Transition Override

Bit 21 = Auto Breaker Operation Inhibit
Bit 22 = Mains Fail Transfer Inhibit

Bit 23 = Restart Delay Active
Bit 24 = Synchronizer Break Close OK

Bit 25 = Synchronizer Angle OK

Bit 26 = Synchronizer Slip Freq OK
Bit 27 = Synchronizer Volt Match OK

Bit 28 = Synchronizer Active
Bit 29 = Parallel To Mains

Bit 30 = Mains Fail Test
Bit 31 = Take Over Load