Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 94

Advertising
background image

88

9469300991 Rev A

Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Group Register Type Bytes R/W

Unit

Range

AEM 4 RTD Input 4=365
AEM 4 RTD Input 5=366

AEM 4 RTD Input 6=367

AEM 4 RTD Input 7=368
AEM 4 RTD Input 8=369

AEM 4 TC Input 1=370
AEM 4 TC Input 2=371

AVR Output=372
GOV Output=373

LS Output=374

AEM 2 Remote Analog

Output 1

Out-of-Range Activation

Delay

GG

7746

Float

4

R W Second 0 - 300

AEM 2 Remote Analog

Output 1

Parameter Minimum

GG

7748

Float

4

R W n/a

-999999 - 999999

AEM 2 Remote Analog

Output 1

Parameter Maximum

GG

7750

Float

4

R W n/a

-999999 - 999999

AEM 2 Remote Analog

Output 1

Current Minimum

GG

7752

Float

4

R W Milliamp 4 - 20

AEM 2 Remote Analog
Output 1

Current Maximum

GG

7754

Float

4

R W Milliamp 4 - 20

AEM 2 Remote Analog
Output 1

Voltage Minimum

GG

7756

Float

4

R W Volt

0 - 10

AEM 2 Remote Analog
Output 1

Voltage Maximum

GG

7758

Float

4

R W Volt

0 - 10

AEM 2 Remote Analog
Output 1

Alarm Configuration

GG

7760

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

AEM 2 Remote Analog

Output 2

Parameter Selection

GG

7762

Int32

4

R W n/a

No Parameter=0

Oil Pressure=1
Coolant Temp=2

Battery Volts=3
RPM=4

Fuel Level=5
Gen Hz=6

Gen VAB=7
Gen VBC=8

Gen VCA=9

Gen Vavg LL=10
Gen VAN=11

Gen VBN=12
Gen VCN=13

Gen Vavg LN=14
Bus 1 Hz=15

Bus 1 VAB=16

Bus 1 VBC=17
Bus 1 VCA=18

Bus 1 Vavg LL=19
Bus 1 VA=20

Bus 1 VB=21
Bus 1 VC=22

Bus 1 Vavg LN=23

Bus 2 Hz=24
Bus 2 VAB=25

Bus 2 VBC=26
Bus 2 VCA=27

Bus 2 Vavg LL=28
Bus 2 VAN=29

Bus 2 VBN=30

Bus 2 VCN=31
Bus 2 Vavg LN=32

Gen PF=33
Bus 1 PF=34

Bus 2 PF=35
Gen Pos kWh=36

Gen Neg kWh=37
Bus 1 Pos kWh=38

Bus 1 Neg kWh=39

Bus 2 Pos kWh=40
Bus 2 Neg kWh=41

Gen IA=42
Gen IB=43

Gen IC=44
Gen I Avg=45

Bus 1 IA=46

Bus 1 IB=47
Bus 1 IC=48

Bus 1 Iavg=49
Bus 2 IAN=50

Bus 2 IBN=51
Bus 2 ICN=52

Bus 2 Iavg=53

Advertising