Basler Electric DGC-2020HD Modbus Protocol User Manual

Page 263

Advertising
background image

9469300991 Rev A

257

DGC-2020HD Modbus

™ Protocol

Legacy Register Table

Register

Description

Type

Units

Scaling

Factor

R/W

Range

44984-85

MTU Status

Int32

n/a

n/a

R

Bit 0 = Not Used
Bit 1 = Not Used

Bit 2 = Not Used
Bit 3 = Not Used

Bit 4 = Not Used

Bit 5 = Not Used
Bit 6 = Not Used

Bit 7 = Not Used
Bit 8 = Not Used

Bit 9 = Not Used
Bit 10 = Not Used

Bit 11 = Not Used
Bit 12 = Not Used

Bit 13 = Not Used

Bit 14 = Not Used
Bit 15 = Not Used

Bit 16 = Not Used
Bit 17 = Not Used

Bit 18 = Not Used
Bit 19 = Not Used

Bit 20 = ECU Shutdown

Bit 21 = Priming Pump ON
Bit 22 = CAN Mode Feedback

Bit 23 = Preheat Temp Not Reached
Bit 24 = Load Gen On

Bit 25 = Cylinder Cutout
Bit 26 = Engine Running

Bit 27 = Speed Decrease

Bit 28 = Speed Increase
Bit 29 = Speed Demand Fail Mode

Bit 30 = External Stop Active
Bit 31 = ECU Override

44986

Generator Frequency

Int32

Hertz

Deci

R

0 - 4400

44988

Bus Frequency

Int32

Hertz

Deci

R

0 - 4400

44990

Power Factor

Int32

n/a

Centi

R

(-100) - 100

44992

Slip Frequency

Int32

n/a

Milli

R

(-450000) -450000

44994-98

Reserved

45000-01

ECU Lamp Status

Int32

n/a

n/a

R

Bit 0 = Protect
Bit 1 = Not Used

Bit 2 = Not Used
Bit 3 = Warning

Bit 4 = Stop
Bit 5 = Not Used

Bit 6 = Not Used

Bit 7 = Malfunction
Bit 8 = Not Used

Bit 9 = Not Used
Bit 10 = Not Used

Bit 11 = Not Used
Bit 12 = Not Used

Bit 13 = Not Used

Bit 14 = Not Used
Bit 15 = Not Used

Bit 16 = Not Used
Bit 17 = Not Used

Bit 18 = Not Used
Bit 19 = Not Used

Bit 20 = Not Used

Bit 21 = Not Used
Bit 22 = Not Used

Bit 23 = Not Used
Bit 24 = Not Used

Bit 25 = Not Used
Bit 26 = Not Used

Bit 27 = Not Used
Bit 28 = Not Used

Bit 29 = Not Used

Bit 30 = Not Used
Bit 31 = Not Used

45002

Reserved

45004

Number of DTC’s

Int32

n/a

n/a

R

(-32768) – 32767

45006-326

Reserved

45328

Engine Parameter Transmit Enable

Int32

n/a

n/a

RW 0 = Disable

1 = Enable

45330

Requested MTU SMC ENG Operating Mode

Int32

n/a

n/a

RW 1 - 2

45332

SPN Conversion Method

Int32

n/a

n/a

RW 1 - 4

45334-498

Reserved

45500

Analog Input 1 Metering Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45502

Analog Input 2 Metering Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

45504

Analog Input 3 Metering Value

Int32

CentiUnit

Centi

R

(-100000000) – 99999900

Advertising