DGC-2020HD Modbus

™ Protocol

Legacy Register Table

Register

Description

Type

Units

Scaling Factor

R/W

Range

42418

Remote Speed Bias Source

Int32

n/a

n/a

RW

0 = None

1 = Local Analog Input 1
2 = Local Analog Input 2

3 = Local Analog Input 3
4 = Local Analog Input 4

5 = AEM 1 Analog Input 1
6 = AEM 1 Analog Input 2

7 = AEM 1 Analog Input 3

8 = AEM 1 Analog Input 4
9 = AEM 1 Analog Input 5

10 = AEM 1 Analog Input 6
11 = AEM 1 Analog Input 7

12 = AEM 1 Analog Input 8
13 = AEM 2 Analog Input 1

14 = AEM 2 Analog Input 2

15 = AEM 2 Analog Input 3
16 = AEM 2 Analog Input 4

17 = AEM 2 Analog Input 5
18 = AEM 2 Analog Input 6

19 = AEM 2 Analog Input 7
20 = AEM 2 Analog Input 8

21 = AEM 3 Analog Input 1

22 = AEM 3 Analog Input 2
23 = AEM 3 Analog Input 3

24 = AEM 3 Analog Input 4
25 = AEM 3 Analog Input 5

26 = AEM 3 Analog Input 6
27 = AEM 3 Analog Input 7

28 = AEM 3 Analog Input 8

29 = AEM 4 Analog Input 1
30 = AEM 4 Analog Input 2

31 = AEM 4 Analog Input 3
32 = AEM 4 Analog Input 4

33 = AEM 4 Analog Input 5
34 = AEM 4 Analog Input 6

35 = AEM 4 Analog Input 7
36 = AEM 4 Analog Input 8

42420-23

Reserved

42424

Load Sharing Aux Input Source

Int32

n/a

n/a

RW

0 = Local Aux Input

1 = System Manager

42426

kW Ramp Status

Int32

n/a

n/a

R

0 - 2

42428

kvar Ramp Status

Int32

n/a

n/a

R

0 - 2

Pulse Outputs

Register

Description

Type

Units

Scaling Factor

R/W

Range

42500

AVR Correction Pulse Width

Int32

Decisecond

Deci

RW

0 - 999

42502

AVR Correction Pulse Interval

Int32

Decisecond

Deci

RW

0 - 999

42504

AVR Bias Contact Type

Int32

n/a

n/a

RW

0 = Continuous
1 = Proportional

42506

Reserved

42508

Governor Correction Pulse Width

Int32

Decisecond

Deci

RW

0 - 999

42510

Governor Correction Pulse Interval

Int32

Decisecond

Deci

RW

0 - 999

42512

Governor Bias Contact Type

Int32

Decisecond

Deci

RW

0 = Continuous
1 = Proportional

Bus Condition Detection

Register

Description

Type

Units

Scaling Factor

R/W

Range

42750

Gen Sensing Dead Bus Pickup

Int32

Volt

n/a

RW

0 - 4800

42752

Gen Sensing Dead Bus Time Delay

Int32

Decisecond

Deci

RW

1 - 6000

42754

Reserved

42756

Gen Sensing Stable Undervoltage Pickup

Int32

Volt

n/a

RW

10 - 99999

42758

Gen Sensing Stable Undervoltage Dropout

Int32

Volt

n/a

RW

10 - 99999

42760

Gen Sensing Stable Overvoltage

Int32

Volt

n/a

RW

10 - 99999

42762

Gen Sensing Stable Overvoltage Dropout

Int32

Volt

n/a

RW

10 - 99999

42764

Gen Sensing Stable Underfrequency Pickup

Int32

CentiHertz

Centi

RW

4600 - 6400

42766

Gen Sensing Stable Underfrequency Dropout

Int32

CentiHertz

Centi

RW

4600 - 6400

42768

Gen Sensing Stable Overfrequency Pickup

Int32

CentiHertz

Centi

RW

4600 - 6400

42770

Gen Sensing Stable Overfrequency Dropout

Int32

CentiHertz

Centi

RW

4600 - 6400

42772

Gen Sensing Fail Time Delay

Int32

Decisecond

Deci

RW

1 - 6000

42774

Gen Sensing Stable Time Delay

Int32

Decisecond

Deci

RW

1 - 6000

42776

Reserved

42778

Bus Sensing Dead Bus Pickup

Int32

Volt

n/a

RW

0 - 4800

42780

Bus Sensing Dead Bus Time Delay

Int32

Decisecond

Deci

RW

1 - 6000

42782

Reserved