246

9469300991 Rev A

Legacy Register Table

DGC-2020HD Modbus

™ Protocol

Register

Description

Type

Units

Scaling

Factor

R/W

Range

44814-15

Pre-Alarm Metering 1

Int32

n/a

n/a

R

Bit 0 = Not Used
Bit 1 = Not Used

Bit 2 = Not Used
Bit 3 = Not Used

Bit 4 = Global Pre-Alarm

Bit 5 = Fuel Filter 2 Leak
Bit 6 = Fuel Filter 1 Leak

Bit 7 = Engine kW Overload 3
Bit 8 = Engine kW Overload 2

Bit 9 = MPU Fail
Bit 10 = Fuel Leak Detect

Bit 11 = Battery Charger Failure
Bit 12 = Low Coolant Level

Bit 13 = Mains Brkr Fail to Open

Bit 14 = Mains Brkr Fail to Close
Bit 15 = Sync Fail at Mains Brkr

Bit 16 = Gen Brkr Fail to Open
Bit 17 = Gen Brkr Fail to Close

Bit 18 = Sync Fail at Gen Brkr
Bit 19 = High Fuel Level

Bit 20 = Loss of Rem. Mod. Com

Bit 21 = Engine kW Overload
Bit 22 = Diagnostic Trouble Code

Bit 23 = Loss of ECU Comms
Bit 24 = Maintenance Due

Bit 25 = Battery Overvoltage
Bit 26 = Weak Battery

Bit 27 = Low Battery Voltage

Bit 28 = Low Coolant Temp
Bit 29 = Low Fuel Level

Bit 30 = Low Oil Pressure
Bit 31 = Hi Coolant Temp

44816-17

MTU Alarm Metering

Int32

n/a

n/a

R

Bit 0 = Not Used
Bit 1 = Not Used

Bit 2 = Not Used
Bit 3 = Not Used

Bit 4 = Not Used
Bit 5 = Not Used

Bit 6 = Not Used

Bit 7 = Not Used
Bit 8 = Not Used

Bit 9 = Not Used
Bit 10 = Not Used

Bit 11 = Not Used
Bit 12 = Not Used

Bit 13 = Not Used

Bit 14 = Not Used
Bit 15 = Not Used

Bit 16 = Not Used
Bit 17 = Not Used

Bit 18 = Not Used
Bit 19 = Not Used

Bit 20 = Not Used

Bit 21 = Not Used
Bit 22 = Not Used

Bit 23 = High ECU Supply
Bit 24 = Combined Red

Bit 25 = Overspeed
Bit 26 = Low Oil Pressure

Bit 27 = Low Fuel Delivery Press.
Bit 28 = Low Aftercooler Coolant Level

Bit 29 = High Coolant Temp

Bit 30 = High Oil Temp
Bit 31 = High Charge Air Temp