9469300991 Rev A

Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Group Register

Type

Bytes R/W

Unit

Range

RS485 Settings

Baud Rate

GG

6600

Uint32

4

R W n/a

1200 Baud=1200
2400 Baud=2400

4800 Baud=4800

9600 Baud=9600
19200 Baud=19200

38400 Baud=38400
57600 Baud=57600

115200 Baud=115200

RS485 Settings

Parity

GG

6602

Uint32

4

R W n/a

Even Parity=0

Odd Parity=1
No Parity=2

RS485 Settings

Bits Per Character

GG

6604

Uint32

4

R W n/a

8-Bits=8
7-Bits=7

RS485 Settings

Stop Bits

GG

6606

Uint32

4

R W n/a

1 Stop Bit=1
2 Stop Bits=2

Ethernet 0 Settings

Subnet Mask

GG

6608

IP

Address

4

R W n/a

n/a

Ethernet 0 Settings

Gateway Address

GG

6610

IP

Address

4

R W n/a

n/a

Ethernet 0 Settings

Use DHCP

GG

6612

Uint32

4

R W n/a

Off=0

On=1

Ethernet 0 Settings

Active IP

GG

6614

IP

Address

4

R

n/a

n/a

Ethernet 0 Settings

Active Gateway

GG

6616

IP

Address

4

R

n/a

n/a

Ethernet 0 Settings

Active Subnet

GG

6618

IP
Address

4

R

n/a

n/a

Ethernet 1 Settings

Subnet Mask

GG

6620

IP
Address

4

R W n/a

n/a

Ethernet 1 Settings

Gateway Address

GG

6622

IP
Address

4

R W n/a

n/a

Ethernet 1 Settings

Use DHCP

GG

6624

Uint32

4

R W n/a

Off=0

On=1

Ethernet 1 Settings

Active IP

GG

6626

IP

Address

4

R

n/a

n/a

Ethernet 1 Settings

Active Gateway

GG

6628

IP

Address

4

R

n/a

n/a

Ethernet 1 Settings

Active Subnet

GG

6630

IP

Address

4

R

n/a

n/a

Modbus

Modbus Ethernet Unit ID

GG

6632

Uint16

2

R W n/a

1 - 247

Modbus

Modbus Serial Unit ID

GG

6633

Uint16

2

R W n/a

1 - 247

Reserved

6634-39

Engine Source

Speed Mode

GG

6640

Uint32

4

R W n/a

Magnetic Pickup=1

Gen Freq=2
MPU/Gen Freq=3

Engine Source

Flywheel Teeth

GG

6642

Uint32

4

R W n/a

1 - 500

Engine Source

Speed Sender Fail Time Delay

GG

6644

Uint32

4

R W Second 0 - 300