222

9469300991 Rev A

Default Register Table

DGC-2020HD Modbus

™ Protocol

Name

Description

Group Register Type Bytes R/W

Unit

Range

Config Protection 6

Threshold 1 Type

GG

24992

Int32

4

R W n/a

Disabled=0
Over=1

Under=2

Config Protection 6

Threshold 1 Pickup

GG

24994

Float

4

R W n/a

-999999 - 999999

Config Protection 6

Threshold 1 Activation Delay

GG

24996

Float

4

R W Second

0 - 300

Config Protection 6

Threshold 1 Alarm Configuration GG

24998

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Config Protection 6

Threshold 2 Type

GG

25000

Int32

4

R W n/a

Disabled=0

Over=1

Under=2

Config Protection 6

Threshold 2 Pickup

GG

25008

Float

4

R W n/a

-999999 - 999999

Config Protection 6

Threshold 2 Activation Delay

GG

25010

Float

4

R W Second

0 - 300

Config Protection 6

Threshold 2 Alarm Configuration GG

25012

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Config Protection 6

Threshold 3 Type

GG

25014

Int32

4

R W n/a

Disabled=0

Over=1
Under=2

Config Protection 6

Threshold 3 Pickup

GG

25016

Float

4

R W n/a

-999999 - 999999

Config Protection 6

Threshold 3 Activation Delay

GG

25018

Float

4

R W Second

0 - 300

Config Protection 6

Threshold 3 Alarm Configuration GG

25020

Uint32 4

R W n/a

Status Only=0

Pre-Alarm=1
Alarm=2

Config Protection 6

Threshold 4 Type

GG

25022

Int32

4

R W n/a

Disabled=0
Over=1

Under=2

Config Protection 6

Threshold 4 Pickup

GG

25024

Float

4

R W n/a

-999999 - 999999

Config Protection 6

Threshold 4 Activation Delay

GG

25026

Float

4

R W Second

0 - 300

Config Protection 6

Threshold 4 Alarm Configuration GG

25028

Uint32 4

R W n/a

Status Only=0
Pre-Alarm=1

Alarm=2

Config Protection 6

Low-Line Scale Current

GG

25030

Float

4

R W n/a

0.001 - 3

Config Protection 6

Low-Line Scale Voltage

GG

25032

Float

4

R W n/a

0.001 - 3

Config Protection 6

Label

GG

25034

String 16

R W n/a

0 - 16

Config Protection 7

Parameter Selection

GG

25036

Int32

4

R W n/a

No Parameter=0

Oil Pressure=1
Coolant Temp=2

Battery Volts=3
RPM=4

Fuel Level=5
Gen Hz=6

Gen VAB=7

Gen VBC=8
Gen VCA=9

Gen Vavg LL=10
Gen VAN=11

Gen VBN=12
Gen VCN=13

Gen Vavg LN=14
Bus 1 Hz=15

Bus 1 Vab=16

Bus 1 Vbc=17
Bus 1 Vca=18

Bus 1 Vavg LL=19
Bus 1 Va=20

Bus 1 Vb=21
Bus 1 Vc=22

Bus 1 Vavg LN=23

Bus 2 Hz=24
Bus 2 VAB=25

Bus 2 VBC=26
Bus 2 VCA=27

Bus 2 Vavg LL=28
Bus 2 Van=29

Bus 2 Vbn=30

Bus 2 Vcn=31
Bus 2 Vavg LN=32

Gen PF=33
Bus 1 PF=34

Bus 2 PF=35
Gen Pos kWh=36

Gen Neg kWh=37

Bus 1 Pos kWh=38
Bus 1 Neg kWh=39

Bus 2 Pos kWh=40
Bus 2 Neg kWh=41

Gen IA=42
Gen IB=43

Gen IC=44