GT 600 / 601 Engineer’s Reference Guide

Wiring Modes available are:-

8 (2 Wire)

Two wires are used for the zone and a global tamper is used.
(Depending on panel version).

(EOL)

Two wires are used in conjunction with two resistors to give
End Of Line wiring, this is the most secure wiring format.

For information on how to wire the various wiring modes please refer to the back
of this manual or refer to the Quick Start Guide that is supplied with the control
panel.

If selecting 8(EOL) follow steps 8 - 10. If selecting 8(2 Wire) jump to step 11.

8)

With the display showing:-
Press Yes.

9)

The display will show:-

Three wiring options are available under 8 (EOL):

Norm:

Standard GardTec wiring configuration without Mask or Fault detection.

Note: Does not give any Fault or Masking detection and should only be used with Zone pairing.

ELF1:

ELF1 wiring is used for detectors that have a relay output (a pair of terminals)
for Fault or Mask..

ELF2:

ELF2 wiring is used for detectors that have a transistor output (a single
terminal) for Fault or Mask.

Note: We would recommend that either ELF1 Format or ELF2 Format (depending on detector output type,
Relay or Transistor) is used. ELF1 or ELF2 wiring modes will allow for Alarm, Tamper, Fault and Masking to be
monitored from a single zone without the need for zone pairing. Please see the back of this manual or refer to
the GT 600 / 601 Quick Start Instructions.

Note: The installer should check what output type the detector are, noting that all the detectors should be of the

same type with regards to the Fault / Mask output.

10)

Press No until the setting you require is displayed
then press Yes. The display will show:-
(Jump to step 15).

On-Board Zones
=8 <EOL>

On-Board EOL
=Norm

Zone Expansion
= ZEX