GT 600 / 601 Engineer’s Reference Guide

ET (Exit Terminator) Mode (default = Set)
If ET Mode = Set then the exit terminator zone will terminate the exit procedure.
If ET Mode = Door Lock and the ET zone (door lock) is operated on entry then all
confirmed alarms will be disabled.

Bell Mode (default = Unconfirmed)
This option controls the bells fitted to the system, options are confirmed or un-
confirmed.
If Bell Trigger = Confirmed then Bell will only trigger with a confirmed alarm.
If Bell Trigger = Unconfirmed then Bell will trigger with un-confirmed alarms.
This feature is not mandatory for DD243

Strobe Mode (default = Unconfirmed)
This option controls the Strobe(s) fitted to the system, options are confirmed or un-
confirmed.
If Strobe Trigger = Confirmed then Strobe will only trigger with a confirmed alarm.
If Strobe Trigger = Unconfirmed then Strobe will trigger with un-confirmed alarms.
This gives the ability to show to the keyholder from outside the premises that a
previously unconfirmed alarm has is now confirmed.
This feature is not mandatory for DD243

Confirmed Start Delay (default = 000m)
May be programmed between 0 & 120 minutes (default 0).
If programmed to anything other than 0 the panel cannot send confirmed signals until
the time programmed has expired. This time starts when the system has set and will
prevent confirmed alarms being generated in situations when a person has been
accidentally locked in the building.
This feature is not mandatory for DD243

Ace Low Battery (default = On)
Options are On or Off. This option allows for the use of new control panel boards with
V5.1 or later software to be used with earlier keypads. If older non DD243 compliant
type keypads are used with V5.1 or later this option should programmed to Off. It is a
requirement of DD243 2002 that when using ACE Low Battery is reported to the end
user if the system is set using ACE.
See A.1 DD243 Portable ACE used for setting and unsetting.

Secondary Zones
The Program Part / Test /Chime option has now been renamed to Program Zone
Attributes. Within this section you are able to allocate zones as Secondary Zones.
Secondary type zones would be used for detectors that may be deemed as having an
over sensitive nature, this will stop unwanted user call-outs. Zones that are entered as
Secondary will follow the chain of events below.

Comms Restore
With Comms Restore turned on any outstanding alarm channels will be restored at the
end of the Confirm Time Window.
This feature is mandatory for DD243