GT 600 / 601 Engineer’s Reference Guide

14)

Press No until the setting required for V.Min is
displayed, then press Yes.
The display will show:-

15)

Press No until the required setting for On-Charge
Volts max (Battery) is displayed, then press Yes.
The display will show:-

16)

Press No until the required setting for On-Charge
Volts min (Battery) is displayed then press Yes.
The display will show:-

17)

Press No until the required setting for Off-Charge
Volts max (Battery) is displayed, then press Yes.
The display will show:-

18)

Press No until the required setting for Off-Charge
Volts min (Battery) is displayed, then press Yes.
The display will show:-

19)

Press Yes. The display will show:-

20)

Press Yes. The display will show:-

PSU . . .
Diagnostics ?

PSU Test Time
= 01 Hrs

Change / List
Test Limits ?

On - Chg. max = 14.0
On - Chg. min = 11.8

Off - Chg. max = 14.0
Off - Chg. min = 11.8

Off - Chg. max = 14.0
Off - Chg. min > 11.8

On - Chg. max = 14.0
On - Chg. min > 11.8