6-1

Section 6
Programming Overview

This section of the manual is intended to give you an overview of the programming
process. Please read this section of the manual carefully, especially if you are
programming the control panel for the first time.

The JumpStart AutoProgramming feature automates many programming tasks and
selects default options for the system. You should run JumpStart at least once when
you are installing the system. See Section 6.1 for details. After you run JumpStart,
you may need to do some additional programming depending on your installation.
Section 7 of this manual covers manual programmable options in detail.

Programming the panel can be thought of as a three part process. You must program:

System options. These are options that affect general operation of the panel (see
Section 7.7 for details).

Options for input points and zones. These are primarily options that control the
detection behavior of devices (see Section 7.6 for details).

Options for output points and groups. This includes selecting characteristics for
output groups and mapping output circuits to output groups (see Section 7.6 for
details).

6.1

JumpStart Autoprogramming

The JumpStart AutoProgramming feature allows for faster system setup. When you
run JumpStart (immediately after addressing SLC devices), the system scans devices
on all SLC loops and determines device type (for example, ionization smoke detector
or heat sensor) and selects some system options based on the device type.
JumpStart AutoProgramming saves the installer from having to program options for
each device. Depending on the application, the installer may need to make some
changes after JumpStart completes.

See Section 6.1.3 for complete details about running JumpStart AutoProgramming.

IMPORTANT

JumpStart is intended to be run one time only, immediately after SLC devices have been addressed and
connected. JumpStart will reset all manually programmed options to default settings. Do not run JumpStart
after you have configured the system.