4.14.2 City Box Connection Using the 5220 Module

This section describes how to connect the control panel to a local energy municipal
fire alarm box or “city box” as required by NFPA 72 Auxiliary Protected Fire Alarm
systems for fire alarm service. The city (master) box is an enclosure that contains a
manually operated transmitter used to send an alarm to the municipal communication
center which houses the central operating part of the fire alarm system.

City Box Standby Current:

0 (Notification supervision current

accounted for in control panel draw.)

Alarm Current:

1 Amp for 1 second
27.2 VDC max

The maximum coil and wire resistance (combined) must not exceed 30 ohms.

To install the 5220 for city box connection:

1. Use one of the knockouts on the right side of the control panel to connect the

5220 using a short piece of conduit (must not exceed 20 feet in length).

2. Wire the 5220 to the control panel as shown in Figure 4-41. This drawing also

shows how to connect the city box coil to terminals 3 and 4 on the 5220. Do not
install an EOL resistor in the terminals of the Flexput circuit used for this applica-
tion.

3. Connect earth ground wire to the 5220 chassis with mounting screw.

4. Program the Flexput circuit used as a notification circuit, continuous and non-

silencing. Refer to Section 7.6.1 for zone grouping and mapping.

It is not possible to reset the remote indication until you clear the condition and reset