Agency Listings, Approvals, and Requirements

151209

2-3

2.2

Underwriters Laboratories (UL)

2.2.1

Requirements for All Installations

General requirements are described in this section. When installing an individual
device, refer to the specific section of the manual for additional requirements. The
following subsections list specific requirements for each type of installation (for
example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems,
and so on). See Section 8.7 for information on releasing operation.

1. All field wiring must be installed in accordance with NFPA 70 National Electric

Code.

2. Use the addressable smoke detectors specified in Section 5.2 of this manual and/

or conventional detectors listed in the compatibility chart. (See Appendix A.)

3. Use UL listed notification appliances compatible with the 5820XL from those

specified in the Appendix at the back of this manual.

4. A full system checkout must be performed any time the panel is programmed.

Restricted Options:

The loss of AC signal is defaulted to 3 hours, however the system allows settings
from 0 - 30 hours. For UL certified installations this number must be set from 1 to
3 hours.

The system allows the use of non-latching spot type smoke detectors. This fea-
ture may not be used in commercial applications whereby a general alarm is
sounded. It is intended for elevator recall, door holding applications, and hotel/
motel room applications.

The system allows the Alarm Verification time to be set from 1 to 255 seconds.
For UL certified installations the setting must be a minimum of 60 seconds.

Call forwarding shall not be used.

When two count is used: detector spacing shall be cut in half, you shall not use
the alarm verification feature, and no delay shall be used.

P.A.S (positive alarm sequence) feature shall be used only with automatic detec-
tors.