IntelliKnight 5820XL Installation Manual

3-8

151209

3.6.1.1 Current Draw Worksheet for SK SLC Devices

Use Table 3-2 to determine current requirements during alarm/battery standby
operation when SK SLC devices are installed. You can install up 99 SK detectors per
loop (396 max per panel) and 99 SK modules per loop (396 max per panel). Copy this
section if additional space is required.

Table 3-2: Current Draw Worksheet for SK SLC Devices

Device

# of Devices

Current per Device

Standby

Current

Alarm

Current

For each device use this formula: This column X This column = Current per number of
devices.

Fire Panel (battery current
draw)

1

Standby: 215 mA

215 mA

Alarm: 385 mA

385 mA

Addressable SLC Detectors

SK-Photo

(99 max/loop

& 396 max/

panel)

1

Standby: .30 mA
Alarm: 6.5 mA

mA

mA

SK-Photo-T

mA

mA

SK-Ion

mA

mA

SK-Heat

mA

mA

SK-Heat-HT

mA

mA

SK-Acclimate

mA

mA

SK-Heat-ROR

mA

mA

SK-Duct

5

(includes PhotoR)

mA

mA

SK-Beam (without integral test)

SLC

Standby/Alarm: 2 mA

Aux. Pwr

Standby: 2 mA

mA

Alarm: 8.5 mA

mA

SK-Beam-T

4

(with integral test)

SLC

Standby/Alarm: 2 mA

Aux. Pwr

Standby: 2 mA

mA

Alarm: 8.5 mA

mA

SK-FIRE-CO

SLC

Standby: .30mA

mA

Alarm: 7.2mA

mA