Dry Contact Wiring

The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of
switch supported by the control panel can be used with the 5880. For example, you
can use a 5880 to monitor pull stations, water flow, tamper, reset, or silence switches.

Wire dry contacts as shown in Figure 4-23. Notice grouping of terminals; power
terminals are shared by two inputs.

Figure 4-23 Dry Contact Wiring

Model 7628

Supervised/Power Limited

4.7k

EOL