3 nfpa 72 polarity reversal, 1 using the 5220 module, 3 nfpa 72 polarity reversal -45 – Honeywell INTELLIKNIGHT 5820XL User Manual

Page 85: 1 using the 5220 module -45

Advertising
background image

Control Panel Installation

151209

4-45

the control panel.

Figure 4-41 City Box Connection

4.14.3 NFPA 72 Polarity Reversal

Note: Intended for connection to a polarity reversal circuit of a control unit at the protected premises

having compatible rating.

4.14.3.1 Using the 5220 Module

When the 5220 is wired and programmed for polarity reversal, it reports alarm and
trouble events to a remote site. Alarms will override trouble conditions and it will not
be possible to reset the remote indicator until the condition is cleared and the control
panel is reset.

If an alarm condition occurs, the alarm relay will close, overriding the trouble
condition.

Standby Current:

100 mA, 24 VDC

Alarm:

100 mA, 24 VDC

To install the 5220 for polarity reversal, follow the steps below:
1. Locate the knockout on the right side of the control panel cabinet to connect the

5220 using a short piece of conduit (must not exceed 20 feet in length).

2. Wire the 5220 to the control panel using the four-wire pigtail provided as shown in

Figure 4-42. This diagram also shows how to connect the 5220 to the remote indi-
cator. Do not install an EOL resistor in the terminals of the Flexput circuit used for
this application.

3. Connect earth ground wire to the 5220 chassis with mounting screw.

Note:
Flexput Circuit 1 used
as an example.
Any Flexput circuit
could be used.

All circuits non-power-limited.

All wiring non-supervised.