IntelliKnight 5820XL Installation Manual

6-2

151209

6.1.1

Input Points

JumpStart will determine the number and type of input points (detectors or contact
monitor modules) on each SLC loop. JumpStart assigns the correct detector type
(heat, ionization or photoelectric), so the installer does not need to edit the device
type for detectors. Any contact monitor modules on the system will be assigned type
“Manual Pull.” The installer will need to manually change the switch type if manual
pull is not correct.

JumpStart creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is
mapped to Output Group 1. After JumpStart completes, you can re-map to configure
a multiple zone/output group system (see Section 7.4.1.3). For a general explanation
of mapping, see Section 6.2.

6.1.2

Output Points

JumpStart creates three output groups and assigns output circuits as follows:

Circuits 1-6:
Configured as Notification and assigned to Group 1. JumpStart automatically
programs Zone 1 to activate Group 1 using constant on output.

Circuit 7 (Relay 1):
Assigned to Group 249. JumpStart automatically programs Zone 1 to activate Group
249 using constant on output when a supervisory condition occurs.

Circuit 8 (Relay 2):
Assigned to Group 250. JumpStart automatically programs Zone 1 to activate Group
250 using constant on output when an alarm occurs.

Addressable output points (Relay modules, NAC Modules, Sounder Bases, Relay
Bases):
All addressable relay devices will be configured as “Output Pt” (general purpose
output point) and assigned to Group 1.

Note: Relay output is constant even if the zone activating the relay is programmed with an output pat-

tern.