3 zone outputs, 3 zone outputs -8, N 7.4.1.3 – Honeywell INTELLIKNIGHT 5820XL User Manual

Page 134

Advertising
background image

IntelliKnight 5820XL Installation Manual

7-8

151209

Heat Temperature Setting

Use this feature to set the temperature at which heat detectors will respond. The
range is 135° to 150° F. All detectors in the zone will respond in the same way.

The Model SD505-AHS Heat Detector is an absolute temperature device. This
means that it responds to an alarm immediately if the temperature in the zone goes
above the programmed temperature.

5. Enter the temperature at which the heat detector will respond.

Or

Use the

or

keys to scroll through the range or enter directly from the num-

ber keys on the annunciator, then press

.

6. Use the

or

keys to scroll through the range or enter directly from the num-

ber keys on the annunciator.

7. Then press

.

7.4.1.3 Zone Outputs

Output groups and cadence patterns are mapped to events. They can be
programmed to output when an event occurs in a zone. Some system trouble events
can be mapped for the entire system. Section 6.2 of this manual contains a general
explanation of mapping. The following sections explain how to select mapping
options.

Note: Use of multiple notification groups may not synchronize with each other.

ENTER

ACK

ENTER

ACK