Miscellaneous Options 1

Through this programming option you can set the water flow delay time, low AC
report delay, enable or disable automatic daylight savings time adjustment, clock
format, and AC clock frequency.

7.7.4.1 Water Flow Delay

You can program a delay of 0-90 seconds (zero means no delay) to be used in
conjunction with a water flow switch. The delay is system-wide. All water flow
switches on the system will use the same delay period.

To access the screen for programming water flow delay, follow these steps:

1. Enter the installer code.

2. Press

or

to display the main menu.

3. Select

for Program Menu.

4. Select

for System Options.

5. Select

for Miscellaneous Options 1.

A screen similar to the one shown in Figure 7-16 will display.

Figure 7-16 Water Flow Delay Programming Screen

6. Enter the number of seconds (0 to 90) to delay an a water flow switch alarm, then

press .

ENTER

ACK

Delay in seconds
before waterflow
alarm occurs.
(00 - 90)