14 remote station applications, 1 keltron model 3158 installation, 14 remote station applications -42 – Honeywell INTELLIKNIGHT 5820XL User Manual

Page 82: 1 keltron model 3158 installation -42

Advertising
background image

IntelliKnight 5820XL Installation Manual

4-42

151209

4.14 Remote Station Applications

4.14.1 Keltron Model 3158 Installation

The control panel is compatible with Keltron Model 3158, used for direct connection
to a Keltron receiver. The 3158 reports alarms, supervisories, and troubles.

The steps for connecting the 3158 to the control panel. Refer to the 3158 installation
instructions for complete information.

1. Wire the 3158 to the control panel as shown in the connection list and Figure 4-

40.

2. Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in con-

duit.

3. Program control panel Relay 1 for alarm.

4. Program Flexput circuit 5 for alarm.

5. Program Flexput circuit 6 for supervisory non latching.

Table 4-3: Keltron 3158 to Control Panel Connections

Terminal #

Connects To

Terminal #

Connects To

3158 Term. 1

To Keltron receiving
equipment

3158 Term. 8

Control panel Term. 28

3158 Term. 2

To Keltron receiving
equipment

3158 Term. 9

Control panel Term. 5

3158 Term. 3

Earth ground

3158 Term. 10

Control panel Term. 4

3158 Term. 4

Not used; no connection.

Control panel Term.
6

Control panel Term. 29

3158 Term. 5

Control panel Term. 18

Control panel Term.
28

Control panel Term. 31

3158 Term. 6

Control panel Term. 19

Control panel Term.
29

Control panel Term. 30

3158 Term. 7

Control panel Term. 7

Advertising