4 wiring requirements for slc devices, 1 wiring 5815xl in style 4 (class b) configuration, Wiring requirements for slc devices -4 – Honeywell INTELLIKNIGHT 5820XL User Manual

Page 94: Ices to the 5815xl (see section 5.4)

Advertising
background image

IntelliKnight 5820XL Installation Manual

5-4

151209

5.4

Wiring Requirements for SLC Devices

The following information applies to all SLC devices. Refer to the section that
describes the type of device you are installing for details.

5.4.1

Wiring 5815XL in Style 4 (Class B) Configuration

No special wire is required for addressable loops. The wire can be untwisted,
unshielded, solid or stranded as long as it meets the National Electric Code 760-51
requirements for power limited fire protective signaling cables. Wire distances are
computed using copper wire.

Maximum wiring resistance is 40 ohms for SK devices and 50 ohms for SD devices.

Maximum loop length depends on the wire gauge. See Table 5-1 and Table 5-2.

Table 5-2 Maximum wiring distance for SD devices

Table 5-1 Maximum wiring distance for SK modules

Wire Gauge

Max. Distance for SK

22 AWG

1200 feet

18 AWG

3100 feet

16 AWG

4900 feet

14 AWG

7900 feet

12 AWG

10,000 feet

Wire Gauge

Max. Distance for SD

22 AWG

1500 feet

18 AWG

3900 feet

16 AWG

6200 feet

14 AWG

10,000 feet

Advertising