Honeywell INTELLIKNIGHT 5820XL User Manual

Page 157

Advertising
background image

Programming

151209

7-31

9. Press the

or

arrow to select the reporting format, then press

.

Events to Report

The next six options select which types of events (or event families) will be reported
to this account. (See Figure 7-12 for location of these options on the screen.) Events
are reported by zone.

10. Press the

or

arrow to select Must, Yes, or No (see table below), then press

.

11. Repeat step 10 for all six event report options.

For each event family, select M, Y, or N.

Switch Attempts

Specify the number of times the dialer should attempt to report to this account before
switching to the next account. Range is 01-05.

Event Family

Events Included in this Family

Alarms

All alarms (Water Flow, Manual Pull, Detectors, Auxiliary Switches)

Alarm Restore

All alarm restores

Supervisory/Trouble

All trouble and supervisory conditions and trouble and supervisory
restores

Enable/Disable Point

Enabling and disabling of input and output points

Service/Test

Fire drill, walk test, dialer test, automatic test, all programming
sessions

System Reset

All system resets

M(ust)

Must Report. Selecting “M” makes this a primary reporting account for this family of events. The
dialer MUST report events in this family to this account.
Selecting Must makes an account a primary reporting account. The dialer will try to report the
event to the primary account until it exceeds the “Switch Attempts” value. When the dialer has
exceeded the Switch Attempt retry limit, it will switch to a backup account (a “Can Report” or
“Yes” account, see below). If the dialer cannot report the event to any of the backup accounts, it
will return to the primary account until it reaches the “Fail Attempts” value of 10. If the Fail
Attempts limit is exceeded, an Account Trouble condition is generated and a local trouble will
sound.

Y(es)

Can Report. Selecting Y makes this a backup account for this event family. The dialer will report
to this account only if it was previously unable to report the event to a Must account.

N(o)

No events in this family will ever be reported to this account.

ENTER

ACK

ENTER

ACK

Advertising