IntelliKnight 5820XL Installation Manual

8-18

151209

for zone option programming.

8.7.1

Single Interlock Zone Releasing

A single interlock zone utilizes a minimum of two addressable detectors and a
designated manual release switch.

Conditions Required for an Pre-Alert Output Activation

If any single addressable detector is activated, the “Pre-Alert” output will activate.
This alerts the user that the initial stages required for a release condition are present.
(Also refer to Table 8-3.)

Conditions required for an General Alarm and Release Output Activation

If two or more addressable detectors, or a manual release switch activate, the
“Alarm” and the “Release” outputs will activate. (Also refer to Table 8-3.)

Important!

Only addressable detectors can be used. No conventional detectors can be used.

Each Single Interlock Zone input requires at least one manual release switch.

Table 8-3: Single Interlock Zone Operation

Inputs

Output Results

1st Addressable Detector

x

x

x

x

2nd Addressable Detector

x

x

x

x

Manual Release Station

x

x

x

x

Nor

m

al

Pr

e-A

ler

t

Pr

e-A

ler

t

R

e

lea

s

e and Genera

l Al

arm

R

e

lea

s

e and Genera

l Al

arm

R

e

lea

s

e and Genera

l Al

arm

R

e

lea

s

e and Genera

l Al

arm

R

e

lea

s

e and Genera

l Al

arm