6 operation mode behavior, Operation mode behavior -12 – Honeywell INTELLIKNIGHT 5820XL User Manual

Page 186

Advertising
background image

IntelliKnight 5820XL Installation Manual

8-12

151209

Note: Detector status can also be viewed and printed using the 5660 SKSS or 5670 SKSS (facility mon-

itoring only).

8.6

Operation Mode Behavior

The control panel can be in one of seven conditions at any given moment: Normal,
Alarm, Prealarm, Supervisory, Trouble, Silenced, and Reset. Table 8-1 describes the
behavior of the panel in each of these modes.

= Print Detector

Status

Prints the current status of all detectors in the system. This is a method for finding out if
any detectors are out of NFPA compliance or any detectors need maintenance (are
approaching an out of compliance condition).

Sample Detector

Status Print-Out

Table 8-1: Operation Mode Behavior

Operation

Mode

Occurs

When

System Behavior

In This Mode You Can

Normal

No alarm or
trouble
condition
exists and
menus are
not in use.

SYSTEM POWER LED is on.

The All Systems Normal display indicates that
the system is in normal mode.

The current date and time display on the last
line of the LCD.

Enter the appropriate code to activate the User
or Installer Menu, or rotate the key to activate
the User Menu.