IntelliKnight 5820XL Basic Operating Instructions

These instructions must be framed and displayed next to the IntelliKnight 5820XL panel in
accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems.

Operation

Keystrokes

Silence alarms and
troubles

Press

then rotate the key or enter a code

Reset alarms

Press

then rotate the key or enter a code.

Conduct a fire drill

1. Rotate the key or enter a code then press

to access the menu.

2. Press .

3. Press

to select Fire Drill.

4. Press any key to begin the drill. To end the drill, press any key.
To conduct a fire drill from a remote fire drill switch:
Activate the switch to begin the drill; de-activate the switch to end the drill.

View alarms and
troubles

When the system is in alarm or trouble, press

to view location and type of alarm or trouble.

View status of point

1. Rotate the key or enter a code then press

to access the menu.

2. Press .

3. Press

for Point Status.

4. From the list that displays, select the 5815XL module where the point you want to view is

located. The screen that displays tells the status of the point including whether detector sen-
sitivity is in compliance (see below).

Check detector
sensitivity

1. Rotate the key or enter a code then press

to access the menu.

2. Press .

3. Press

for Point Status.

4. From the list that displays, select the 5815XL module where the point you want to view is

located.

5. The fourth line of the display shows the sensitivity status.
“NORMAL” means the detector is in compliance with NFPA 72.
“CAL MAINT” means the detector is in compliance with NFPA 72 but
maintenance should be performed soon.
“CAL TRBLE” means the detector is not in compliance with NFPA 72.

Set time and date

1. Rotate the key or enter a code then press

to access the menu.

2. Press .
3. Make changes in the fields on the screen as necessary.

4. When the time and date are correct, press

.

Enable / Disable point

1. Rotate the key or enter a code to access to access Main Menu.

2. Press

to select Point Functions.

3. Press

for Disable / Enable Pt.

4. Press

for Disable / Enable Pt.

5. Use the

or

to move through the list. Then press

to select the module where the

point you want to disable/enable is located

6. Enter the point or circuit number that you want to disable/enable.

7. Press

key to toggle between NORMAL (enable) or DISABLE.