Programming

151209

7-11

Zone Mapping Example

Suppose you want to program Zone 1 so that:

Any alarm (detector, water flow or manual pull) would activate Output Group 1
using the ANSI cadence pattern.

Manual pull alarm would activate Output Group 3 using constant output.

Troubles would activate Output Group 2 using the zone-coded cadence pattern.

To accomplish this you need to access the screen for each event and then select your
output groups. Figure 7-4 shows how you would program this application.

Figure 7-4 Zone Mapping Example