Control Panel Installation

151209

4-35

4.12.2.2 Class A Inputs

You can connect conventional Class A switches, such as waterflow switches and pull
stations, directly to the Flexput circuits of the control panel.

To install a Class A switch:

1. Wire the Class A switch as shown in Figure 4-33.

2. Configure the circuit through programming (see Section 7.6).

Figure 4-33 Class A initiating Switches

Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is

used to refer to the circuit pair. For example, Figure 4-33 uses both Flexput circuit 5 and 6, so in
programming it would be referred to as point 5.

Note:
Flexput circuit 5 and 6
used as an example.
Any Flexput point pairing
could be used.

Supervised
Power Limited