IntelliKnight 5820XL Installation Manual

5-8

151209

5.6

Addressing SK SLC Devices

All SK devices are addressed using the two rotary dials that appear on the device
board. Use the ONES rotary dial to set the ones place in a one or two digit number,
and use the TENS rotary dial to set the tens place in a two digit number.

SK device addresses are handled differently than SD device addresses. The control
panel recognizes when an SK detector or SK module is installed. For this reason, SK
detectors can be assigned any address from 1 to 99, and SK modules can also be
assigned any address from 1 to 99. For example SK-Photo (detector) can be
addressed as 1 and SK-Monitor (module) and also be addressed as 1. (0 is a invalid
address).

SD detectors and modules use unique addresses 1 through 127.

Example 1: To select device address 1, turn the ONES rotary dial to 1 and the TENS
rotary dial to 0 as shown in Figure 5-5.

Example 2: To select device address 42, turn the ONES rotary dial to 2 and the
TENS rotary dial to 4 as show in Figure 5-5.

Figure 5-5 SK SLC Device Addressing Using Rotary Dials

Example 1: Device Set to 01.

Example 2: Device Set to 42.

All dials labeled for ONES

or TENS position.