3.6.1.2 Current Draw Worksheet for SD SLC Devices

Use Table 3-3 to determine current requirements during alarm/battery standby
operation when SD SLC devices are installed. You can install up 127 SD devices per
loop (508 max per panel). Copy this section if additional space is required.

Table 3-3: Current Draw Worksheet for SD SLC Devices

Device

# of Devices

Current per Device

Standby

Current

Alarm

Current

For each device use this formula: This column X This column = Current per number of devices.

IntelliKnight 5820XL Fire Panel
(Current draw from battery)

1

Standby: 215 mA

215 mA

Alarm: 385 mA

385 mA

Addressable SLC Devices
SD500-AIM

(508 max.)

1

Standby/Alarm: .55 mA

mA

mA

SD500-MIM

mA

mA

SD500-PS
SD500-ARM

mA

mA

SD505-AHS

mA

mA

SD505-AIS

mA

mA

SD505-APS

mA

mA

SD500-ANM

(508 max.)

1

Aux. Pwr

Standby: 8 mA

mA

Alarm: 60 mA

mA

SLC

Standby/Alarm: .55 mA

mA

mA

SD500-SDM

(508 max.)

1

SLC

Standby/Alarm: .55 mA

mA

Aux. Pwr

Standby: 20 mA

mA

Alarm: 106 mA

mA

SD500-LED

(100 max.)

1

Aux. Pwr

Standby: 10 mA

mA

Alarm: 220 mA

mA

LED: 10 mA

mA

mA

SLC

Standby/Alarm: .55 mA

mA

mA

SLC Accessory Bases
SD505-6RB

(508 max.)

Standby/Alram: .082 mA

mA

mA

SD505-6SB

(508 max.)

Aux. Pwr

Standby: 1 mA

mA

Alarm: 32 mA

mA

SLC

Standby/Alarm .082 mA

mA

mA

SD505-DUCTR

(508 max.)

Aux. Pwr

Standby: 20 mA

2

mA

Alarm: 62 mA

2

mA

SLC

Standby/Alarm: .5 mA

mA

mA

SD505-DTS-K

(508 max.)

None, included with SD505-DUCTR worst case.

SD505-DUCT

(508 max.)

None, included with detector current.

SLC Isolator Devices
SD500-LIM

(1024 max.)

Standby/Alarm .092 mA

mA

mA

SD505-6IB

(508 max.)

Accessories Modules
5815XL SLC Expander

(3 max.)

Standby/Alarm: 55 mA

mA

mA

5860 Remote Fire Alarm Annun.

(8 max.)

Standby: 20 mA

mA

Alarm: 25 mA

mA

5824 Serial/Parallel Printer
Interface

(2 max.)

Standby/Alarm: 45 mA

mA

mA

5895XL IntelliKnight Power
Expander

(8 max.)

Standby/Alarm: 10 mA

mA

mA

5496 Intelligent Power Module

Standby/Alarm: 10 mA

mA

mA