Programming

151209

7-9

Mapping to Zone Events

Eight types of events can occur in zones. For each event type, you can activate up to
8 output groups or output group template, specifying a pattern for each. The following
is a list of all event types:

Note: Abbreviations in the parenthesizes are the characters that are displayed in programming (see

Figure 7-3).

Manual Pull Alarm (MP)

Water Flow Alarm (WF)

Detector Alarm (DE). This applies to heat or smoke detectors.

Aux 1 and Aux 2 Alarm (A1 or A2). User-specified alarm types.

Pre-alarm (PR)

Supervisory (SU)

Trouble (TR)

Status Point (SP)

CO Alarm (CO)

CO Supervisory (SCO)

To map zone events to outputs:

1. From the Installer Main Menu, select

for Program Menu.

2. From the Program Menu, select

for Zone.

3. From the next menu, select

for Edit Zone.

4. Enter the zone number you wish to edit.

5. From the next menu, select

for Zone Outputs.

6. From the next screen, a list of 8 event types will display. Select the event type you

want to program. A screen similar to the one shown in Figure 7-3 will display.

Press .

7. Press the

or

key to toggle the group letter to either G = Group or T = output

group template depending on want you need for this zone. Press

.

ENTER

ACK

ENTER

ACK