Honeywell INTELLIKNIGHT 5820XL User Manual

Page 143

Advertising
background image

Programming

151209

7-17

Silencing Options

The following silencing options are available for each output group.

Response with System-Wide Conditions

You can select whether an output group will respond to various system-wide
occurrences. (See Figure 7-8 for location of this field.)

11. To get to this menu item repeat steps 1 through 6 of Section 7.5.1.

Table 7-2: Silencing Options

Option

Description

SILENCE

Silenceable. The output group can be silenced through the

key.

NON-SIL

Not silenceable. The output group cannot be silenced. Activation of the

key will

be ignored for this output group.

AUT UNSIL

Auto Unsilenced. If this option is selected, the output group can be silenced for a
programmed time-frame. If the condition that caused the output to activate has not cleared
during the time-frame, the output reactivates. If you select this option, select the time-frame
in the DLY: field. Range is 00-60 minutes. (See Figure 7-8 for location of field.)

SIL-INHIB

Timed Silence after Inhibit. If this option is selected, the output group must be audible for a
programmed number of minutes before it can be silenced. If the condition that caused the
output to activate has not cleared during the time-frame, the output can be silenced. If you
select this option, select the timeframe in the DLY: field. Range is 00-60 minutes. (See
Figure 7-8 for location of field.)

SHUT-DOWN

If this option is selected, the output group will automatically silence (shut down) after the
programmed time period. If you select this option, select the timeframe in the DLY: field.
Range is 01-60 minutes. (See Figure 7-8 for location of field.)

Table 7-3: Output Group Response Choices

Option

Description

ManPull

Manual Pull Activation. Select Yes if you want this group to activate for all manual pull
alarms that occur in the system.

Note:

Even though manual pull switches are assigned to zones, activation selected

here for manual pull will override zone-programmed activation.

Fire Drill

Fire Drill Activation. Select Yes if you want this group to activate for fire drills.

Sys Aux1 and Sys Aux2

Select Yes if you want this output group to activate for system-wide Aux1 and Aux2
alarms. (Aux 1 and Aux 2 alarm types are for auxiliary alarm conditions. For example,
you might want to use Aux 1 to provide a unique alarm type.)

Ignore Global Cad

Ignore Global Cadence. If you want to create an output group that can never be
overridden, you can select Yes for this option. Selecting No means that system-wide
events that have been assigned an output pattern could override the pattern for the
output group.
For example, suppose you had assigned a set of strobes to Output Group 3. You
would never want these strobes to output in a pattern under any circumstances. To
make sure this happens, select Yes for Ignore Global Cadence for Output Group 3.

Reverse Polarity

This option programs the output group for reverse polarity operation. Selecting
Reverse Polarity–Troubles will cause the output group to be de-energized for any
system trouble. Selecting Reverse Polarity–No Troubles will cause system troubles to
be ignored. Activation is accomplished through standard mapping methods. Use with
the 7644 assembly to implement reverse polarity. See Section 4.14.3.2 for more
information on the 7644.

SILENCE

SILENCE

Advertising