Honeywell INTELLIKNIGHT 5820XL User Manual

Page 34

Advertising
background image

IntelliKnight 5820XL Installation Manual

3-10

151209

1. Total does not include isolator devices or accessory bases.

2. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is

removed during that time. However, during normal operation, door holders draw current and must be included in the
6.0A total current that can be drawn from the panel.

3. Use next size battery with capacity greater than required.

4. SK-Beam-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be

considered when determining auxiliary power capacity but not calculated into current requirements for day to day
operation.

5. The SK-Duct housing contains a vacant mount for a SK-Relay (sold separately). Current draw for the SK-Relay is

calculated by increasing the SK-Relay row of the calculation sheet by one for each SK-Relay used with a SK-Duct.

5865-4 LED Annunciator
(with reset and silence
switches)

(8 max.)

Standby: 35 mA

mA

Alarm: 145 mA

mA

5865-3 LED Annunciator

Standby: 35 mA

mA

Alarm: 145 mA

mA

5880 I/O Module

Standby: 35 mA

mA

Alarm: 200 mA

mA

5883 Relay Interface

(32 max.)

Standby: 0 mA

mA

Alarm: 220 mA
(22 mA per relay)

mA

A

Total System Current

Auxiliary Devices

2

Refer to devices manual for current rating.

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

B

Auxiliary Devices Current

Notification Appliance Circuits

Refer to device manual for current rating.

Alarm: mA

mA

Alarm: mA

mA

Alarm: mA

mA

Alarm: mA

mA

C

Notification Appliances Current

mA

D

Total current ratings of all devices in system (line A + line B + C)

mA

mA

E

Total current ratings converted to amperes (line D x .001):

A

A

F

Number of standby hours:

H

G

Multiply lines E and F.

Total standby AH

AH

H

Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)

H

I

Multiply lines E and H.

Total alarm AH

AH

J

Add lines G and I.

3

Total ampere hours

required

AH

Device

# of Devices

Current per Device

Standby

Current

Alarm

Current

Advertising