Coil with Ohmmeter
1.
Set R x 1000.
2. Connect leads as shown.
3. Reading: Should register some value,

Approx. 200-1000 ohms.

What It Means –
Infinity reading indicates coil is open. Zero

reading indicates coil is shorted. In either case,

the coil should be replaced.
A reading of 200-1000 ohms indicates coil is

ok.

!

WARNING!

Open master breaker and disconnect all

leads from starter to avoid damage to

meter or electric shock hazard. Connect

the ohmmeter leads as shown above.