Mo tor insula tion resis tance – Xylem GSSERVICE R2 Service Manual Submersible Pumps & Jet Pumps User Manual

Page 36

Advertising
background image

1. Set the scale lever to R x 100K and

adjust to 0.

2. Connect an ohmmeter lead to any one of
the motor leads and the other to the metal
drop pipe. If the drop pipe is plastic, connect
the ohmmeter lead to the metal well casing
or ground wire.

CAUTION

Open (turn off) master breaker and

disconnect all leads from control box or

pressure switch (Q-D type control, remove

lid) to avoid damage to meter or electric

shock hazard.

OHMS

R x 1000

R x 10K

R x 100K

R x 100
R x 10
R x 1

ZERO

OHMS

R x 100K

Drop

Cable

with

Ground

Wire

34

MO

TOR INSULA

TION RESIS

TANCE