Three phase unbalance – Xylem GSSERVICE R2 Service Manual Submersible Pumps & Jet Pumps User Manual

Page 91

Advertising
background image

THREE PHASE UNBALANCE

89

Calculate percentage of current unbalance for

all three hookups.

Example:

Hook Up 1

Hook Up 2

Hook Up 3

T1= 51 Amps

T3 = 50 Amps T2 = 50 Amps

T2 = 46 Amps

T1= 48 Amps T3 = 49 Amps

T3 = 53 Amps

T2 = 52 Amps T1= 51 Amps

Add up all three readings for hook up number 1.
T1 = 51 Amps

T2 = 46 Amps

+T3 = 53 Amps

Total 150 Amps

Divide the total by three to obtain the average.

50 Amps = Average

3 150 Amps

Calculate the greatest amp difference from the aver-
age. Could be greater than average.

50 Amps

-46 Amps

4 Amps

Divide this difference by the average to obtain the

percentage of unbalance.

.08 or 8%

50 4.00 Amps

Hook Up #1 = 8%

Hook Up #2 = 4%

Hook Up #3 = 2%

Always use hook up with lowest % current unbalance.
Loads on a transformer bank vary. Readings should be
taken at peak load period.

What It Means –

1. Hook ups below 5% = system balanced.
2. Hook ups not below 5% – if the unbalance moves with

the motor leads the unbalance is caused by the motor,

wet splice, or damaged cable. Check the motor on

pages 44-45. If the unbalance remains with the termi-

nals the unbalance is in the power supply – contact

power company.

Advertising