Three phase unbalance, Caution, Rule of thumb – Xylem GSSERVICE R2 Service Manual Submersible Pumps & Jet Pumps User Manual
Page 90: Supply starter motor
Advertising
88
L1
L2
L3
T1
T2
T3
1st Hookup
Starter
L1
L2
L3
T3
T1
T2
2nd Hookup
Supply
Starter
L1
L2
L3
T2
T3
T1
3rd Hookup
Starter
Motor
!
CAUTION
To prevent changing motor rotation, the
motor leads should be reordered in the
same direction, see example on page 51.
RULE OF THUMB
If the unbalance moves with the motor
leads the unbalance is caused by the
motor, wet splice, or damaged cable. If
the unbalance remains with the terminals
the unbalance is in the power supply
.
For the best protection, we recommend no more
than a 5% current deviation from average current.
Current readings in amps should be checked on
each leg using the three possible hookups.
L1
L2
L3
T1
T2
T3
Supply
Starter
Motor
L
1
L
2
L
3
T
1
T
2
T
3
THREE PHASE UNBALANCE