Three phase unbalance, Caution, Rule of thumb – Xylem GSSERVICE R2 Service Manual Submersible Pumps & Jet Pumps User Manual

Page 90: Supply starter motor

Advertising
background image

88

L1

L2

L3

T1

T2

T3

1st Hookup

Starter

L1

L2

L3

T3

T1

T2

2nd Hookup

Supply

Starter

L1

L2

L3

T2

T3

T1

3rd Hookup

Starter

Motor

!

CAUTION

To prevent changing motor rotation, the

motor leads should be reordered in the

same direction, see example on page 51.

RULE OF THUMB

If the unbalance moves with the motor
leads the unbalance is caused by the
motor, wet splice, or damaged cable. If
the unbalance remains with the terminals
the unbalance is in the power supply

.

For the best protection, we recommend no more

than a 5% current deviation from average current.
Current readings in amps should be checked on

each leg using the three possible hookups.

L1

L2

L3

T1

T2

T3

Supply

Starter

Motor

L

1

L

2

L

3

T

1

T

2

T

3

THREE PHASE UNBALANCE